ED-DP-345AC7-B24 C
17.20 kW
Defrost: None
Product code: ED-DP-245AE4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,349 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 97.4 m² |
| Inner volume | 21.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 135 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| ED-DP-245AE4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.23 | 7.19 | 7.21 | 7.26 | 7.28 | 7.26 | 7.22 | 7.41 | 7.90 | 8.60 | 8.45 | 8.40 | 8.34 | 8.26 |
| 5 | 9.29 | 9.32 | 9.39 | 9.48 | 9.52 | 9.49 | 9.42 | 9.58 | 10.18 | 11.05 | 10.77 | 10.67 | 10.53 | 10.32 |
| 6 | 11.31 | 11.44 | 11.60 | 11.77 | 11.84 | 11.83 | 11.74 | 11.87 | 12.58 | 13.64 | 13.23 | 13.07 | 12.84 | 12.47 |
| 7 | 13.32 | 13.58 | 13.81 | 14.08 | 14.21 | 14.23 | 14.13 | 14.24 | 15.08 | 16.32 | 15.80 | 15.59 | 15.27 | 14.75 |
| 8 | 15.19 | 15.62 | 16.03 | 16.41 | 16.61 | 16.65 | 16.57 | 16.67 | 17.65 | 19.07 | 18.47 | 18.21 | 17.82 | 17.15 |
| 9 | 16.91 | 17.51 | 18.09 | 18.62 | 18.95 | 19.10 | 19.04 | 19.14 | 20.26 | 21.88 | 21.18 | 20.88 | 20.41 | 19.61 |
| 10 | 18.48 | 19.29 | 20.04 | 20.71 | 21.07 | 21.30 | 21.35 | 21.52 | 22.80 | 24.65 | 23.94 | 23.59 | 23.04 | 22.11 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.937 |
| SC2 | 0 | 8 | 16.673 |
| SC3 | -18 | 7 | 14.145 |
| SC4 | -25 | 6 | 11.604 |
| SC5 | -34 | 6 | 11.353 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.