ED-DP-163AE7-B27 C
14.82 kW
Defrost: None
Product code: ED-DP-245AE7-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,886 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 61.0 m² |
| Inner volume | 20.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 122 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 380 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | A |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| ED-DP-245AE7-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.64 | 5.71 | 5.79 | 5.87 | 5.90 | 5.89 | 5.86 | 5.99 | 6.38 | 6.93 | 6.79 | 6.75 | 6.69 | 6.60 |
| 5 | 7.22 | 7.42 | 7.61 | 7.78 | 7.87 | 7.90 | 7.86 | 7.99 | 8.49 | 9.21 | 8.97 | 8.89 | 8.77 | 8.59 |
| 6 | 8.77 | 9.12 | 9.45 | 9.71 | 9.89 | 9.97 | 9.96 | 10.09 | 10.71 | 11.62 | 11.29 | 11.16 | 10.97 | 10.67 |
| 7 | 10.17 | 10.71 | 11.20 | 11.64 | 11.92 | 12.07 | 12.10 | 12.25 | 13.00 | 14.11 | 13.70 | 13.54 | 13.30 | 12.90 |
| 8 | 11.40 | 12.11 | 12.77 | 13.35 | 13.70 | 13.95 | 14.09 | 14.31 | 15.21 | 16.53 | 16.16 | 15.97 | 15.69 | 15.19 |
| 9 | 12.51 | 13.42 | 14.15 | 14.91 | 15.44 | 15.80 | 15.99 | 16.26 | 17.28 | 18.78 | 18.38 | 18.19 | 17.89 | 17.37 |
| 10 | 13.52 | 14.64 | 15.57 | 16.48 | 17.15 | 17.62 | 17.89 | 18.21 | 19.36 | 21.04 | 20.61 | 20.40 | 20.06 | 19.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.611 |
| SC2 | 0 | 8 | 14.309 |
| SC3 | -18 | 7 | 11.768 |
| SC4 | -25 | 6 | 9.449 |
| SC5 | -34 | 6 | 8.859 |
| A | 1948 mm |
|---|---|
| B | 1050 mm |
| C | 405 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 1635 mm |
| E2 | 818 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1948 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.