ED-DP-440AE4-B22 C
23.27 kW
Defrost: None
Product code: ED-DP-345AC4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 10,730 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 97.0 m² |
| Inner volume | 19.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 168 kg |
| Quantity | 3 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 570 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | B |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø35 |
| ED-DP-345AC4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.63 | 8.74 | 8.84 | 8.95 | 8.98 | 8.97 | 8.91 | 9.10 | 9.68 | 10.50 | 10.29 | 10.23 | 10.14 | 9.96 |
| 5 | 11.21 | 11.50 | 11.78 | 11.99 | 12.11 | 12.13 | 12.06 | 12.25 | 13.01 | 14.10 | 13.74 | 13.62 | 13.44 | 13.19 |
| 6 | 13.56 | 14.09 | 14.60 | 15.05 | 15.35 | 15.46 | 15.43 | 15.61 | 16.53 | 17.92 | 17.43 | 17.25 | 16.97 | 16.54 |
| 7 | 15.56 | 16.36 | 17.09 | 17.65 | 18.09 | 18.35 | 18.46 | 18.73 | 19.90 | 21.63 | 21.13 | 20.93 | 20.62 | 20.12 |
| 8 | 17.41 | 18.38 | 19.37 | 20.24 | 20.85 | 21.23 | 21.41 | 21.72 | 23.08 | 25.07 | 24.50 | 24.25 | 23.88 | 23.25 |
| 9 | 18.89 | 20.36 | 21.63 | 22.76 | 23.56 | 24.08 | 24.36 | 24.73 | 26.28 | 28.55 | 27.92 | 27.63 | 27.19 | 26.43 |
| 10 | 20.51 | 22.21 | 23.79 | 25.21 | 26.22 | 26.91 | 27.31 | 27.76 | 29.51 | 32.06 | 31.39 | 31.06 | 30.56 | 29.67 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 31.385 |
| SC2 | 0 | 8 | 21.716 |
| SC3 | -18 | 7 | 17.846 |
| SC4 | -25 | 6 | 14.598 |
| SC5 | -34 | 6 | 13.690 |
| A | 2748 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 540 mm |
| E1 | 2435 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø35 |
| Length | 2748 mm |
|---|---|
| Width | 1050 mm |
| Height | 540 mm |
Our engineers answer with a selection for your conditions.