ED-DP-445AE7-B24 C
30.63 kW
Defrost: None
Product code: ED-DP-445AC4-B24 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 14,310 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 129.9 m² |
| Inner volume | 29.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 218 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 900 rpm |
| Power | 760 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | B |
| Inlet | Ø28 |
|---|---|
| Outlet | Ø54 |
| ED-DP-445AC4-B24 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 11.75 | 11.71 | 11.73 | 11.80 | 11.80 | 11.76 | 11.68 | 11.93 | 12.70 | 13.79 | 13.54 | 13.46 | 13.32 | 13.11 |
| 5 | 15.36 | 15.49 | 15.66 | 15.83 | 15.88 | 15.83 | 15.72 | 15.95 | 16.94 | 18.36 | 17.91 | 17.76 | 17.56 | 17.26 |
| 6 | 18.97 | 19.35 | 19.72 | 20.06 | 20.19 | 20.20 | 20.08 | 20.28 | 21.50 | 23.28 | 22.62 | 22.37 | 22.02 | 21.48 |
| 7 | 22.25 | 22.93 | 23.59 | 24.22 | 24.61 | 24.74 | 24.65 | 24.84 | 26.33 | 28.51 | 27.64 | 27.31 | 26.83 | 26.05 |
| 8 | 25.13 | 26.14 | 27.09 | 27.84 | 28.40 | 28.73 | 28.83 | 29.16 | 30.96 | 33.60 | 32.78 | 32.44 | 31.87 | 30.87 |
| 9 | 27.83 | 29.05 | 30.34 | 31.47 | 32.24 | 32.67 | 32.87 | 33.24 | 35.29 | 38.28 | 37.37 | 36.96 | 36.35 | 35.31 |
| 10 | 30.33 | 31.96 | 33.59 | 35.04 | 36.01 | 36.62 | 36.92 | 37.37 | 39.67 | 43.02 | 42.02 | 41.55 | 40.85 | 39.64 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 42.016 |
| SC2 | 0 | 8 | 29.160 |
| SC3 | -18 | 7 | 24.398 |
| SC4 | -25 | 6 | 19.719 |
| SC5 | -34 | 6 | 19.072 |
| A | 3548 mm |
|---|---|
| B | 1050 mm |
| C | 435 mm |
| F | 1090 mm |
| G | 570 mm |
| E1 | 3235 mm |
| E2 | 818 mm |
| E3 | 800 mm |
| D IN | 1 x Ø28 |
| D OUT | 1 x Ø54 |
| Length | 3548 mm |
|---|---|
| Width | 1050 mm |
| Height | 570 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.