Skip to Content

Unit cooler ED-DR-545AA5-A27 C

Unit cooler ED-DR-545AA5-A27 C
Illustrative photo

Producer: Karyer · Line: ED-DR (Banana Ripnening)

Product code: ED-DR-545AA5-A27 C

Cooling capacity i
23.72 kW
Air flow
32,413 m³/h
Fin spacing
5.0 mm
Air throw
26 m
Fans
5 × ⌀450 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): ED-DR — ED-DR - double-flow banana ripening unit cooler
  • B
    Number of fans: 5 — Number of fans (one digit).
  • C
    Fan diameter: 45 — Ø450 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: A — 2 tube rows
  • F
    Fin spacing: 5 — Fin spacing about 5 mm
  • G
    Generation code: A — Generation A
  • H
    Fan data: 27 — Ø450: 400V/3Ph/50Hz, 4-pole

Data

Evaporator
Air flow 32,413 m³/h
Air throw 26 m
External surface 108.1 m²
Inner volume 23.8 dm³
Fin spacing 5.0 mm
Fin materialAluminium
Net weight 251 kg
Fans
Quantity 5
Diameter 450 mm
Speed 1,360 rpm
Power 2,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 60.0 dB(A)
Sound power 82.9 dB(A)
Energy class E
Connections
Inlet Ø28
Outlet Ø42
Defrost
ED-DR-545AA5-A27 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

High speed (Δ)
22.565 kW
Low speed (Y)
20.267 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

High speed (Δ)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 9.17 8.93 8.81 8.77 8.74 8.72 8.70 8.74 9.26 10.04 9.86 9.79 9.70 9.57
5 12.35 12.07 11.93 11.87 11.80 11.72 11.65 11.67 12.36 13.37 13.08 12.97 12.82 12.60
6 15.75 15.51 15.38 15.32 15.23 15.11 14.99 14.97 15.84 17.11 16.68 16.53 16.31 15.99
7 19.17 19.06 19.04 19.06 18.98 18.85 18.68 18.62 19.69 21.25 20.66 20.45 20.14 19.68
8 22.54 22.59 22.73 22.89 22.90 22.80 22.64 22.57 23.86 25.73 24.99 24.71 24.31 23.71
9 25.40 25.75 26.15 26.59 26.86 26.93 26.81 26.74 28.28 30.52 29.64 29.30 28.81 28.05
10 28.12 28.71 29.32 29.91 30.29 30.51 30.62 30.76 32.63 35.37 34.52 34.13 33.56 32.66

Low speed (Y)

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 8.43 8.22 8.12 8.10 8.09 8.08 8.07 8.13 8.63 9.36 9.20 9.15 9.07 8.95
5 11.27 11.01 10.89 10.85 10.80 10.75 10.70 10.76 11.41 12.35 12.10 12.01 11.88 11.69
6 14.31 14.06 13.92 13.89 13.82 13.73 13.64 13.66 14.47 15.65 15.28 15.15 14.97 14.69
7 17.40 17.23 17.16 17.17 17.10 16.98 16.86 16.84 17.83 19.25 18.75 18.57 18.31 17.92
8 20.47 20.44 20.49 20.59 20.56 20.47 20.32 20.27 21.44 23.14 22.50 22.26 21.92 21.40
9 23.42 23.58 23.80 24.04 24.11 24.06 23.93 23.89 25.27 27.28 26.50 26.20 25.77 25.11
10 25.92 26.32 26.77 27.25 27.55 27.72 27.68 27.66 29.26 31.60 30.71 30.36 29.85 29.05

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] High speed (Δ) [kW]Low speed (Y) [kW]
SC1 10 10 34.52130.709
SC2 0 8 22.56520.267
SC3 -18 7 19.03317.145
SC4 -25 6 15.38213.920
SC5 -34 6 15.71514.269

Dimensions

Dimension drawing of ED-DR-545AA5-A27 C
Dimension drawing
Dimensions as drawn
A 5948 mm
B 1215 mm
C 290 mm
F 1165 mm
G 360 mm
E1 1138 mm
E2 1120 mm
E 5635 mm
D IN 1 x Ø28
D OUT 1 x Ø42
Overall [mm]
Length 5948 mm
Width 1215 mm
Height 360 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.