ED-145AC7-C23 C
6.70 kW
Defrost: None
Product code: ED-330AC7-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,213 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 23.8 m² |
| Inner volume | 8.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 73 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.4 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| ED-330AC7-C21 C | None |
|---|---|
| ED-330AC7-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.46 | 2.44 | 2.43 | 2.43 | 2.43 | 2.41 | 2.39 | 2.43 | 2.57 | 2.78 | 2.72 | 2.70 | 2.66 | 2.61 |
| 5 | 3.25 | 3.26 | 3.29 | 3.32 | 3.32 | 3.31 | 3.29 | 3.31 | 3.51 | 3.80 | 3.71 | 3.67 | 3.63 | 3.56 |
| 6 | 4.02 | 4.10 | 4.17 | 4.24 | 4.27 | 4.28 | 4.25 | 4.28 | 4.54 | 4.91 | 4.77 | 4.72 | 4.65 | 4.54 |
| 7 | 4.79 | 4.93 | 5.06 | 5.18 | 5.25 | 5.28 | 5.27 | 5.31 | 5.63 | 6.09 | 5.92 | 5.85 | 5.76 | 5.60 |
| 8 | 5.48 | 5.69 | 5.90 | 6.09 | 6.22 | 6.30 | 6.32 | 6.36 | 6.75 | 7.30 | 7.11 | 7.03 | 6.91 | 6.72 |
| 9 | 6.08 | 6.37 | 6.65 | 6.90 | 7.05 | 7.17 | 7.24 | 7.34 | 7.80 | 8.47 | 8.30 | 8.22 | 8.11 | 7.88 |
| 10 | 6.64 | 7.02 | 7.34 | 7.66 | 7.89 | 8.05 | 8.15 | 8.26 | 8.78 | 9.55 | 9.36 | 9.27 | 9.14 | 8.92 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 9.359 |
| SC2 | 0 | 8 | 6.363 |
| SC3 | -18 | 7 | 5.217 |
| SC4 | -25 | 6 | 4.169 |
| SC5 | -34 | 6 | 4.042 |
| A | 1848 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 1535 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1848 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.