ED-630AE7-C25 C
15.79 kW
Defrost: None
Product code: ED-630AC4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,012 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 75.6 m² |
| Inner volume | 14.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 125 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 720 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| ED-630AC4-C25 C | None |
|---|---|
| ED-630AC4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.94 | 6.16 | 6.36 | 6.54 | 6.63 | 6.67 | 6.65 | 6.82 | 7.27 | 7.91 | 7.75 | 7.71 | 7.64 | 7.55 |
| 5 | 7.51 | 7.91 | 8.28 | 8.60 | 8.79 | 8.89 | 8.89 | 9.06 | 9.64 | 10.46 | 10.21 | 10.11 | 9.98 | 9.77 |
| 6 | 8.83 | 9.40 | 9.94 | 10.34 | 10.66 | 10.87 | 10.98 | 11.19 | 11.91 | 12.97 | 12.70 | 12.58 | 12.42 | 12.14 |
| 7 | 9.99 | 10.64 | 11.40 | 12.04 | 12.50 | 12.81 | 12.97 | 13.22 | 14.06 | 15.32 | 14.99 | 14.85 | 14.63 | 14.26 |
| 8 | ≈ 11.03 | 11.93 | 12.85 | 13.68 | 14.29 | 14.71 | 14.95 | 15.25 | 16.23 | 17.67 | 17.32 | 17.15 | 16.89 | 16.41 |
| 9 | 11.87 | 13.06 | 14.20 | 15.24 | 16.02 | 16.58 | 16.92 | 17.29 | 18.40 | 20.04 | 19.66 | 19.47 | 19.17 | 18.59 |
| 10 | 12.27 | 14.10 | 15.47 | 16.73 | 17.70 | 18.41 | 18.86 | 19.31 | 20.57 | 22.41 | 22.02 | 21.81 | 21.47 | 20.81 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 22.018 |
| SC2 | 0 | 8 | 15.251 |
| SC3 | -18 | 7 | 12.242 |
| SC4 | -25 | 6 | 9.935 |
| SC5 | -34 | 6 | 8.958 |
| A | 3348 mm |
|---|---|
| B | 1030 mm |
| C | 245 mm |
| F | 985 mm |
| G | 305 mm |
| E1 | 3035 mm |
| E2 | 518 mm |
| E3 | 500 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 3348 mm |
|---|---|
| Width | 1030 mm |
| Height | 305 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.