Skip to Content

Unit cooler ED-P-A-125BC4-B24 C

Unit cooler ED-P-A-125BC4-B24 C
Illustrative photo

Producer: Karyer · Line: ED-P A (Commercial Double Flow)

Product code: ED-P-A-125BC4-B24 C

Cooling capacity i
0.88 kW
Air flow
469 m³/h
Fin spacing
3.9 mm
Air throw
2 m
Fans
1 × ⌀250 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): ED-P — ED-P - commercial double-flow ceiling evaporator, plastic cabinet
  • B
    Design type: A — Design type A (grey casing)
  • C
    Number of fans: 1 — Number of fans (one digit).
  • D
    Fan diameter: 25 — Ø250 mm
  • G
    Fin spacing: 4 — Fin spacing about 4 mm
  • H
    Generation code: B — Generation B
  • I
    Fan data: 24 — Ø250: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 469 m³/h
Air throw 2 m
External surface 3.7 m²
Inner volume 0.9 dm³
Fin spacing 3.9 mm
Fin materialAluminium
Net weight 6 kg
Fans
Quantity 1
Diameter 250 mm
Speed 1,300 rpm
Power 65 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 34.0 dB(A)
Sound power 54.7 dB(A)
Energy class E
Connections
Inlet Ø3/8"
Outlet Ø3/8"
Defrost
ED-P-A-125BC4-B24 C None

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
0.848 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 0.32 0.33 0.34 0.35 0.35 0.35 0.35 0.36 0.39 0.42 0.41 0.41 0.41 0.40
5 0.41 0.42 0.44 0.46 0.47 0.47 0.47 0.48 0.51 0.55 0.54 0.53 0.53 0.52
6 0.49 0.52 0.54 0.57 0.58 0.59 0.59 0.60 0.64 0.70 0.68 0.67 0.66 0.64
7 0.56 0.60 0.64 0.67 0.70 0.71 0.72 0.73 0.78 0.84 0.82 0.81 0.80 0.77
8 0.63 0.68 0.73 0.77 0.80 0.82 0.83 0.85 0.90 0.98 0.96 0.95 0.94 0.91
9 ≈ 0.68 0.75 0.81 0.86 0.90 0.93 0.94 0.96 1.02 1.11 1.09 1.08 1.06 1.03
10 ≈ 0.74 0.82 0.89 0.95 1.00 1.04 1.05 1.08 1.15 1.25 1.22 1.21 1.19 1.16

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 1.224
SC2 0 8 0.848
SC3 -18 7 0.683
SC4 -25 6 0.542
SC5 -34 6 0.493

Dimensions

Dimension drawing of ED-P-A-125BC4-B24 C
Dimension drawing
Dimensions as drawn
A 565 mm
B 445 mm
C 160 mm
E 270 mm
D 538 mm
D IN 1 x Ø3/8"
D OUT 1 x Ø3/8"
Overall [mm]
Length 565 mm
Width 445 mm
Height 150 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.