EG-A-325AC6-C25 C
2.03 kW
Defrost: None
Product code: EG-A-323AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,002 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 8.9 m² |
| Inner volume | 1.1 dm³ |
| Fin spacing | 3.8 mm |
| Fin material | Aluminium |
| Net weight | 12 kg |
| Quantity | 3 |
|---|---|
| Diameter | 230 mm |
| Speed | 1,300 rpm |
| Power | 114 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 34.0 dB(A) |
|---|---|
| Sound power | 54.9 dB(A) |
| Energy class | D |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| EG-A-323AC4-C21 C | None |
|---|---|
| EG-A-323AC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.77 | 0.77 | 0.78 | 0.78 | 0.78 | 0.77 | 0.77 | 0.79 | 0.84 | 0.91 | 0.90 | 0.89 | 0.89 | 0.87 |
| 5 | 1.02 | 1.03 | 1.05 | 1.06 | 1.06 | 1.06 | 1.04 | 1.06 | 1.13 | 1.22 | 1.19 | 1.18 | 1.16 | 1.14 |
| 6 | 1.25 | 1.28 | 1.31 | 1.34 | 1.36 | 1.36 | 1.35 | 1.36 | 1.44 | 1.56 | 1.51 | 1.50 | 1.47 | 1.43 |
| 7 | 1.45 | 1.50 | 1.55 | 1.59 | 1.62 | 1.63 | 1.63 | 1.65 | 1.75 | 1.90 | 1.85 | 1.83 | 1.80 | 1.74 |
| 8 | 1.65 | 1.72 | 1.79 | 1.85 | 1.88 | 1.90 | 1.90 | 1.92 | 2.04 | 2.21 | 2.15 | 2.12 | 2.09 | 2.02 |
| 9 | 1.82 | 1.92 | 2.01 | 2.09 | 2.14 | 2.17 | 2.17 | 2.19 | 2.33 | 2.52 | 2.45 | 2.42 | 2.38 | 2.30 |
| 10 | 1.99 | 2.11 | 2.23 | 2.33 | 2.40 | 2.43 | 2.44 | 2.47 | 2.62 | 2.83 | 2.76 | 2.72 | 2.67 | 2.58 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 2.758 |
| SC2 | 0 | 8 | 1.920 |
| SC3 | -18 | 7 | 1.605 |
| SC4 | -25 | 6 | 1.313 |
| SC5 | -34 | 6 | 1.256 |
| A | 1205 mm |
|---|---|
| B | 215 mm |
| C | 465 mm |
| F | 187 mm |
| E | 365 mm |
| D | 441 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 1205 mm |
|---|---|
| Width | 465 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.