EG-A-323BC4-C21 C
2.13 kW
Defrost: None
Product code: EG-A-325AD6-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,317 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 7.4 m² |
| Inner volume | 1.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 15 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| EG-A-325AD6-C25 C | None |
|---|---|
| EG-A-325AD6-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.82 | 0.84 | 0.86 | 0.87 | 0.88 | 0.88 | 0.87 | 0.90 | 0.96 | 1.04 | 1.02 | 1.01 | 1.00 | 0.98 |
| 5 | 1.06 | 1.10 | 1.14 | 1.17 | 1.19 | 1.20 | 1.19 | 1.22 | 1.30 | 1.41 | 1.37 | 1.36 | 1.34 | 1.32 |
| 6 | 1.27 | 1.34 | 1.40 | 1.45 | 1.49 | 1.51 | 1.52 | 1.55 | 1.65 | 1.80 | 1.75 | 1.73 | 1.71 | 1.66 |
| 7 | 1.45 | 1.55 | 1.63 | 1.71 | 1.76 | 1.80 | 1.81 | 1.85 | 1.97 | 2.14 | 2.09 | 2.07 | 2.04 | 1.99 |
| 8 | 1.64 | 1.76 | 1.87 | 1.97 | 2.04 | 2.09 | 2.11 | 2.15 | 2.28 | 2.48 | 2.43 | 2.41 | 2.37 | 2.30 |
| 9 | 1.79 | 1.95 | 2.09 | 2.22 | 2.31 | 2.37 | 2.40 | 2.44 | 2.60 | 2.82 | 2.77 | 2.74 | 2.70 | 2.62 |
| 10 | ≈ 1.93 | 2.12 | 2.29 | 2.45 | 2.55 | 2.63 | 2.68 | 2.74 | 2.91 | 3.17 | 3.11 | 3.08 | 3.03 | 2.94 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.111 |
| SC2 | 0 | 8 | 2.145 |
| SC3 | -18 | 7 | 1.735 |
| SC4 | -25 | 6 | 1.398 |
| SC5 | -34 | 6 | 1.285 |
| A | 1205 mm |
|---|---|
| B | 215 mm |
| C | 490 mm |
| F | 187 mm |
| E | 365 mm |
| D | 441 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 1205 mm |
|---|---|
| Width | 490 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.