EG-A-325BE4-C25 C
2.79 kW
Defrost: None
Product code: EG-A-325AE4-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,141 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 13.3 m² |
| Inner volume | 1.6 dm³ |
| Fin spacing | 3.8 mm |
| Fin material | Aluminium |
| Net weight | 16 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | E |
| Inlet | Ø3/8" |
|---|---|
| Outlet | Ø1/2" |
| EG-A-325AE4-C25 C | None |
|---|---|
| EG-A-325AE4-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.02 | 1.07 | 1.11 | 1.15 | 1.17 | 1.18 | 1.17 | 1.21 | 1.29 | 1.40 | 1.37 | 1.37 | 1.35 | 1.34 |
| 5 | 1.26 | 1.34 | 1.41 | 1.48 | 1.52 | 1.54 | 1.55 | 1.59 | 1.69 | 1.85 | 1.81 | 1.79 | 1.77 | 1.73 |
| 6 | 1.47 | 1.60 | 1.70 | 1.78 | 1.84 | 1.88 | 1.90 | 1.94 | 2.06 | 2.24 | 2.19 | 2.17 | 2.14 | 2.08 |
| 7 | ≈ 1.68 | 1.83 | 1.96 | 2.08 | 2.17 | 2.22 | 2.25 | 2.29 | 2.43 | 2.64 | 2.58 | 2.55 | 2.51 | 2.44 |
| 8 | ≈ 1.85 | 2.04 | 2.21 | 2.37 | 2.46 | 2.54 | 2.58 | 2.63 | 2.80 | 3.05 | 2.98 | 2.95 | 2.89 | 2.81 |
| 9 | ≈ 2.00 | 2.23 | 2.44 | 2.61 | 2.76 | 2.86 | 2.92 | 2.98 | 3.17 | 3.45 | 3.38 | 3.34 | 3.29 | 3.18 |
| 10 | ≈ 1.54 | ≈ 2.40 | 2.61 | 2.86 | 3.04 | 3.17 | 3.25 | 3.33 | 3.55 | 3.86 | 3.78 | 3.74 | 3.68 | 3.56 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.784 |
| SC2 | 0 | 8 | 2.633 |
| SC3 | -18 | 7 | 2.121 |
| SC4 | -25 | 6 | 1.700 |
| SC5 | -34 | 6 | 1.498 |
| A | 1205 mm |
|---|---|
| B | 215 mm |
| C | 517 mm |
| F | 187 mm |
| E | 365 mm |
| D | 441 mm |
| D IN | 1 x Ø3/8" |
| D OUT | 1 x Ø1/2" |
| Length | 1205 mm |
|---|---|
| Width | 517 mm |
| Height | 215 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.