EG-325AB7-C23 C
2.78 kW
Defrost: Electric
Product code: EG-230BB7-C25 C ED
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,472 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 7.4 m² |
| Inner volume | 2.1 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 29 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø15,9 |
| EG-230BB7-C25 C | None |
|---|---|
| EG-230BB7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.02 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 0.99 | 1.01 | 1.07 | 1.15 | 1.12 | 1.11 | 1.10 | 1.08 |
| 5 | 1.35 | 1.37 | 1.38 | 1.40 | 1.40 | 1.40 | 1.39 | 1.41 | 1.49 | 1.61 | 1.57 | 1.56 | 1.54 | 1.51 |
| 6 | 1.67 | 1.72 | 1.76 | 1.80 | 1.82 | 1.83 | 1.82 | 1.84 | 1.95 | 2.11 | 2.05 | 2.03 | 1.99 | 1.95 |
| 7 | 1.96 | 2.04 | 2.11 | 2.17 | 2.22 | 2.24 | 2.26 | 2.29 | 2.43 | 2.64 | 2.56 | 2.54 | 2.50 | 2.43 |
| 8 | 2.24 | 2.33 | 2.42 | 2.51 | 2.58 | 2.62 | 2.64 | 2.67 | 2.84 | 3.09 | 3.03 | 3.00 | 2.96 | 2.89 |
| 9 | 2.49 | 2.62 | 2.75 | 2.86 | 2.94 | 2.99 | 3.02 | 3.07 | 3.26 | 3.54 | 3.47 | 3.44 | 3.39 | 3.31 |
| 10 | 2.71 | 2.89 | 3.05 | 3.19 | 3.30 | 3.37 | 3.41 | 3.46 | 3.68 | 4.00 | 3.92 | 3.88 | 3.83 | 3.74 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.918 |
| SC2 | 0 | 8 | 2.674 |
| SC3 | -18 | 7 | 2.190 |
| SC4 | -25 | 6 | 1.762 |
| SC5 | -34 | 6 | 1.686 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø15,9 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.