EG-230AC4-C21 C
4.41 kW
Defrost: None
Product code: EG-230BC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,426 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 15.7 m² |
| Inner volume | 2.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 31 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 67.8 dB(A) |
| Energy class | C |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EG-230BC4-C21 C | None |
|---|---|
| EG-230BC4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.67 | 1.69 | 1.71 | 1.73 | 1.74 | 1.74 | 1.73 | 1.77 | 1.89 | 2.05 | 2.01 | 2.00 | 1.97 | 1.94 |
| 5 | 2.16 | 2.22 | 2.28 | 2.33 | 2.36 | 2.37 | 2.36 | 2.40 | 2.55 | 2.76 | 2.70 | 2.67 | 2.64 | 2.60 |
| 6 | 2.60 | 2.71 | 2.81 | 2.90 | 2.96 | 3.00 | 3.01 | 3.06 | 3.26 | 3.54 | 3.45 | 3.41 | 3.36 | 3.28 |
| 7 | 3.02 | 3.17 | 3.30 | 3.42 | 3.51 | 3.56 | 3.59 | 3.65 | 3.88 | 4.21 | 4.12 | 4.09 | 4.03 | 3.94 |
| 8 | 3.39 | 3.59 | 3.78 | 3.95 | 4.07 | 4.14 | 4.17 | 4.24 | 4.50 | 4.90 | 4.79 | 4.74 | 4.67 | 4.55 |
| 9 | 3.73 | 3.99 | 4.24 | 4.46 | 4.61 | 4.71 | 4.77 | 4.83 | 5.13 | 5.57 | 5.46 | 5.40 | 5.32 | 5.18 |
| 10 | 4.04 | 4.37 | 4.68 | 4.95 | 5.12 | 5.25 | 5.33 | 5.42 | 5.77 | 6.27 | 6.14 | 6.08 | 5.98 | 5.82 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.142 |
| SC2 | 0 | 8 | 4.236 |
| SC3 | -18 | 7 | 3.463 |
| SC4 | -25 | 6 | 2.809 |
| SC5 | -34 | 6 | 2.629 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.