EM-235AC4-C21 C
17.35 kW
Defrost: None
Product code: EM-235AB4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,416 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 79.0 m² |
| Inner volume | 12.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 106 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.8 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EM-235AB4-C21 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.13 | 5.27 | 5.42 | 5.56 | 5.66 | 5.73 | 5.77 | 5.82 | 6.19 | 6.72 | 6.61 | 6.56 | 6.50 | 6.40 |
| 5 | 6.44 | 6.72 | 6.98 | 7.23 | 7.40 | 7.53 | 7.62 | 7.70 | 8.18 | 8.89 | 8.74 | 8.69 | 8.60 | 8.45 |
| 6 | 7.63 | 8.04 | 8.43 | 8.79 | 9.07 | 9.28 | 9.43 | 9.57 | 10.19 | 11.10 | 10.95 | 10.89 | 10.80 | 10.62 |
| 7 | 8.69 | 9.25 | 9.78 | 10.27 | 10.64 | 10.92 | 11.14 | 11.31 | 12.05 | 13.14 | 12.97 | 12.90 | 12.79 | 12.60 |
| 8 | 9.76 | 10.47 | 11.14 | 11.76 | 12.23 | 12.59 | 12.84 | 13.06 | 13.92 | 15.19 | 15.01 | 14.90 | 14.78 | 14.56 |
| 9 | 10.65 | 11.55 | 12.39 | 13.16 | 13.76 | 14.21 | 14.50 | 14.78 | 15.76 | 17.19 | 17.01 | 16.93 | 16.80 | 16.56 |
| 10 | ≈ 11.46 | 12.54 | 13.57 | 14.51 | 15.14 | 15.72 | 16.16 | 16.51 | 17.62 | 19.25 | 19.07 | 18.98 | 18.84 | 18.58 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.070 |
| SC2 | 0 | 8 | 13.061 |
| SC3 | -18 | 7 | 10.431 |
| SC4 | -25 | 6 | 8.430 |
| SC5 | -34 | 6 | 7.728 |
| A | 4500 mm |
|---|---|
| B | 600 mm |
| C | 462 mm |
| F | 650 mm |
| G | 700 mm |
| E | 1815 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 4500 mm |
|---|---|
| Width | 600 mm |
| Height | 462 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.