EM-235AB4-C21 C
13.55 kW
Defrost: None
Product code: EM-235AC4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,354 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 106.2 m² |
| Inner volume | 18.6 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 120 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.4 dB(A) |
| Energy class | A |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EM-235AC4-C21 C | None |
|---|
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.91 | 7.06 | 7.23 | 7.40 | 7.52 | 7.61 | 7.68 | 7.75 | 8.24 | 8.95 | 8.80 | 8.75 | 8.66 | 8.52 |
| 5 | 8.61 | 8.90 | 9.18 | 9.46 | 9.66 | 9.81 | 9.91 | 10.01 | 10.64 | 11.57 | 11.37 | 11.29 | 11.17 | 10.98 |
| 6 | 10.20 | 10.66 | 11.09 | 11.50 | 11.80 | 12.02 | 12.18 | 12.31 | 13.09 | 14.24 | 14.00 | 13.91 | 13.76 | 13.51 |
| 7 | 11.65 | 12.28 | 12.87 | 13.42 | 13.83 | 14.14 | 14.37 | 14.57 | 15.51 | 16.89 | 16.64 | 16.54 | 16.38 | 16.09 |
| 8 | 12.98 | 13.80 | 14.57 | 15.28 | 15.81 | 16.21 | 16.50 | 16.75 | 17.83 | 19.42 | 19.15 | 19.03 | 18.85 | 18.53 |
| 9 | 14.33 | 15.34 | 16.28 | 17.14 | 17.80 | 18.25 | 18.63 | 18.92 | 20.15 | 21.96 | 21.67 | 21.54 | 21.33 | 20.97 |
| 10 | 15.46 | 16.69 | 17.85 | 18.90 | 19.71 | 20.31 | 20.76 | 21.09 | 22.48 | 24.45 | 24.15 | 24.01 | 23.79 | 23.40 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.148 |
| SC2 | 0 | 8 | 16.747 |
| SC3 | -18 | 7 | 13.600 |
| SC4 | -25 | 6 | 11.092 |
| SC5 | -34 | 6 | 10.309 |
| A | 4500 mm |
|---|---|
| B | 600 mm |
| C | 462 mm |
| F | 650 mm |
| G | 700 mm |
| E | 1815 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 4500 mm |
|---|---|
| Width | 600 mm |
| Height | 462 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.