EA-163ED10-C01 C
9.63 kW
Defrost: None
Product code: EA-163EC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,763 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 45.1 m² |
| Inner volume | 13.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 101 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 74.4 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-163EC7-C01 C | None |
|---|---|
| EA-163EC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.72 | 3.67 | 3.64 | 3.64 | 3.63 | 3.61 | 3.59 | 3.64 | 3.85 | 4.17 | 4.08 | 4.05 | 4.01 | 3.94 |
| 5 | 4.93 | 4.90 | 4.90 | 4.92 | 4.90 | 4.88 | 4.84 | 4.88 | 5.18 | 5.61 | 5.47 | 5.43 | 5.36 | 5.26 |
| 6 | 6.16 | 6.20 | 6.24 | 6.29 | 6.29 | 6.26 | 6.21 | 6.25 | 6.62 | 7.16 | 6.97 | 6.90 | 6.80 | 6.66 |
| 7 | 7.33 | 7.47 | 7.59 | 7.71 | 7.75 | 7.74 | 7.69 | 7.72 | 8.17 | 8.83 | 8.57 | 8.48 | 8.34 | 8.14 |
| 8 | 8.44 | 8.70 | 8.90 | 9.10 | 9.20 | 9.23 | 9.20 | 9.24 | 9.79 | 10.58 | 10.27 | 10.15 | 9.98 | 9.71 |
| 9 | 9.42 | 9.80 | 10.14 | 10.46 | 10.66 | 10.76 | 10.77 | 10.82 | 11.47 | 12.40 | 12.06 | 11.92 | 11.71 | 11.38 |
| 10 | 10.32 | 10.81 | 11.27 | 11.68 | 11.95 | 12.12 | 12.21 | 12.33 | 13.09 | 14.21 | 13.88 | 13.73 | 13.49 | 13.10 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.883 |
| SC2 | 0 | 8 | 9.242 |
| SC3 | -18 | 7 | 7.729 |
| SC4 | -25 | 6 | 6.242 |
| SC5 | -34 | 6 | 6.174 |
| A | 1215 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E | 835 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1215 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.