Skip to Content

Unit cooler EA-250AE4-C09 C

Unit cooler EA-250AE4-C09 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-250AE4-C09 C

Cooling capacity i
25.12 kW
Air flow
11,773 m³/h
Fin spacing
4.2 mm
Air throw
18 m
Fans
2 × ⌀500 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 2 — Number of fans (one digit).
  • C
    Fan diameter: 50 — Ø500 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: E — 6 tube rows
  • F
    Fin spacing: 4 — Fin spacing about 4 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 09 — Ø500: 230V/1Ph/50Hz, 4-pole

Data

Evaporator
Air flow 11,773 m³/h
Air throw 18 m
External surface 103.5 m²
Inner volume 22.3 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 120 kg
Fans
Quantity 2
Diameter 500 mm
Speed 1,330 rpm
Power 1,420 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 81.2 dB(A)
Energy class D
Connections
Inlet Ø22
Outlet Ø42
Defrost
EA-250AE4-C09 C None
EA-250AE4-C09 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
24.182 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 9.59 9.62 9.68 9.74 9.74 9.68 9.59 9.84 10.49 11.38 11.14 11.05 10.93 10.74
5 12.59 12.76 12.99 13.18 13.24 13.19 13.05 13.29 14.12 15.29 14.89 14.76 14.59 14.34
6 15.39 15.92 16.39 16.78 16.96 16.95 16.82 17.02 18.06 19.54 18.93 18.70 18.38 17.89
7 17.83 18.62 19.34 19.97 20.29 20.50 20.53 20.82 22.11 24.00 23.25 22.95 22.51 21.81
8 20.02 21.13 22.02 22.89 23.46 23.78 23.88 24.18 25.67 27.86 27.13 26.83 26.37 25.60
9 22.04 23.36 24.67 25.82 26.61 27.04 27.23 27.59 29.28 31.76 30.95 30.58 30.03 29.10
10 23.75 25.55 27.21 28.67 29.67 30.30 30.59 31.02 32.93 35.71 34.82 34.40 33.76 32.66

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 34.821
SC2 0 8 24.182
SC3 -18 7 20.155
SC4 -25 6 16.393
SC5 -34 6 15.529

Dimensions

Dimension drawing of EA-250AE4-C09 C
Dimension drawing
Dimensions as drawn
A 2087 mm
B 640 mm
C 685 mm
F 445 mm
E1 868 mm
E 1735 mm
D IN 1 x Ø22
D OUT 1 x Ø42
Overall [mm]
Length 2087 mm
Width 640 mm
Height 685 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.