EA-150AE8-C10 C
10.37 kW
Defrost: None
Product code: EA-335AC7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 7,367 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 28.6 m² |
| Inner volume | 9.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 66 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-335AC7-C01 C | None |
|---|---|
| EA-335AC7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.74 | 3.67 | 3.63 | 3.61 | 3.57 | 3.53 | 3.49 | 3.52 | 3.72 | 4.02 | 3.92 | 3.88 | 3.82 | 3.75 |
| 5 | 5.05 | 5.03 | 5.03 | 5.03 | 5.00 | 4.95 | 4.88 | 4.92 | 5.22 | 5.63 | 5.47 | 5.42 | 5.34 | 5.22 |
| 6 | 6.39 | 6.42 | 6.49 | 6.55 | 6.56 | 6.52 | 6.44 | 6.48 | 6.86 | 7.40 | 7.17 | 7.09 | 6.97 | 6.81 |
| 7 | 7.64 | 7.82 | 7.98 | 8.13 | 8.19 | 8.17 | 8.11 | 8.16 | 8.64 | 9.32 | 9.01 | 8.90 | 8.73 | 8.47 |
| 8 | 8.75 | 9.03 | 9.31 | 9.56 | 9.73 | 9.82 | 9.84 | 9.88 | 10.47 | 11.32 | 10.96 | 10.82 | 10.62 | 10.28 |
| 9 | 9.76 | 10.16 | 10.54 | 10.85 | 11.08 | 11.22 | 11.28 | 11.40 | 12.11 | 13.14 | 12.83 | 12.69 | 12.49 | 12.17 |
| 10 | 10.70 | 11.19 | 11.69 | 12.14 | 12.45 | 12.64 | 12.74 | 12.89 | 13.69 | 14.85 | 14.51 | 14.36 | 14.13 | 13.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.510 |
| SC2 | 0 | 8 | 9.884 |
| SC3 | -18 | 7 | 8.159 |
| SC4 | -25 | 6 | 6.491 |
| SC5 | -34 | 6 | 6.407 |
| A | 1857 mm |
|---|---|
| B | 523 mm |
| C | 525 mm |
| F | 345 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 523 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.