Skip to Content

Unit cooler EA-340AC6-C01 C

Unit cooler EA-340AC6-C01 C
Illustrative photo

Producer: Karyer · Line: EA (General)

Product code: EA-340AC6-C01 C

Cooling capacity i
14.05 kW
Air flow
9,543 m³/h
Fin spacing
6.0 mm
Air throw
13 m
Fans
3 × ⌀400 mm

Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %

Model nomenclature

How to read the code of this model.

  • A
    Model code (series): EA — EA - general-purpose unit cooler
  • B
    Number of fans: 3 — Number of fans (one digit).
  • C
    Fan diameter: 40 — Ø400 mm
  • D
    Dimensional data - coil size letter: A — First letter of Karyer's "dimensional data". With the fan count and diameter it fixes the finned coil length and the tubes per row (one casing size). It is a catalogue size index, not a measure: take dimensions from the model datasheet.
  • E
    Dimensional data - tube rows: C — 4 tube rows
  • F
    Fin spacing: 6 — Fin spacing about 6 mm
  • G
    Generation code: C — Generation C
  • H
    Fan data: 01 — Ø300: 230V/1Ph/50Hz, 4-pole; Ø350: 230V/1Ph/50Hz, 4-pole; Ø400: 230V/1Ph/50Hz, 4-pole; Ø450: 230V/1Ph/50Hz, 4-pole; Ø630: 230V/1Ph/50Hz, 6-pole; Ø800: 400V/3Ph/50Hz, 6-pole

Data

Evaporator
Air flow 9,543 m³/h
Air throw 13 m
External surface 42.2 m²
Inner volume 12.6 dm³
Fin spacing 6.0 mm
Fin materialAluminium
Net weight 82 kg
Fans
Quantity 3
Diameter 400 mm
Speed 1,430 rpm
Power 480 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 63.0 dB(A)
Sound power 85.0 dB(A)
Energy class C
Connections
Inlet Ø15,9
Outlet Ø35
Defrost
EA-340AC6-C01 C None
EA-340AC6-C01 C ED Electric

Performance

No glide: dew, mid and bubble point give the same rating.

TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.

R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)

Single phase
13.509 kW

Capacity matrix [kW]

R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.

Single phase

Cooling capacity [kW] per air inlet temperature and TD
TD [K] \ air [°C] -35-30-25-20-15-10-502510121520
4 5.15 5.12 5.11 5.11 5.09 5.04 4.99 5.06 5.35 5.78 5.63 5.58 5.50 5.39
5 6.85 6.92 7.00 7.07 7.07 7.04 6.96 7.04 7.46 8.07 7.85 7.78 7.67 7.53
6 8.53 8.76 8.96 9.13 9.19 9.20 9.14 9.22 9.77 10.56 10.25 10.14 9.98 9.74
7 10.01 10.38 10.73 11.05 11.26 11.39 11.41 11.51 12.19 13.20 12.83 12.69 12.48 12.14
8 11.31 11.85 12.29 12.74 13.05 13.24 13.34 13.51 14.36 15.60 15.26 15.12 14.91 14.55
9 12.51 13.17 13.83 14.43 14.85 15.12 15.27 15.48 16.45 17.88 17.50 17.33 17.07 16.64
10 13.51 14.47 15.32 16.08 16.62 16.99 17.21 17.46 18.57 20.19 19.77 19.57 19.27 18.75

Standard ratings (EN 328 / Eurovent)

Standard condition Air inlet [°C] TD [K] Single phase [kW]
SC1 10 10 19.768
SC2 0 8 13.509
SC3 -18 7 11.149
SC4 -25 6 8.956
SC5 -34 6 8.593

Dimensions

Dimension drawing of EA-340AC6-C01 C
Dimension drawing
Dimensions as drawn
A 2017 mm
B 586 mm
C 605 mm
F 395 mm
E1 568 mm
E2 550 mm
E 1685 mm
D IN 1 x Ø15,9
D OUT 1 x Ø35
Overall [mm]
Length 2017 mm
Width 586 mm
Height 605 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.