EA-150AG4-C09 C
13.94 kW
Defrost: None
Product code: EA-340AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,543 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 42.2 m² |
| Inner volume | 12.6 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 82 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø35 |
| EA-340AC6-C01 C | None |
|---|---|
| EA-340AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.15 | 5.12 | 5.11 | 5.11 | 5.09 | 5.04 | 4.99 | 5.06 | 5.35 | 5.78 | 5.63 | 5.58 | 5.50 | 5.39 |
| 5 | 6.85 | 6.92 | 7.00 | 7.07 | 7.07 | 7.04 | 6.96 | 7.04 | 7.46 | 8.07 | 7.85 | 7.78 | 7.67 | 7.53 |
| 6 | 8.53 | 8.76 | 8.96 | 9.13 | 9.19 | 9.20 | 9.14 | 9.22 | 9.77 | 10.56 | 10.25 | 10.14 | 9.98 | 9.74 |
| 7 | 10.01 | 10.38 | 10.73 | 11.05 | 11.26 | 11.39 | 11.41 | 11.51 | 12.19 | 13.20 | 12.83 | 12.69 | 12.48 | 12.14 |
| 8 | 11.31 | 11.85 | 12.29 | 12.74 | 13.05 | 13.24 | 13.34 | 13.51 | 14.36 | 15.60 | 15.26 | 15.12 | 14.91 | 14.55 |
| 9 | 12.51 | 13.17 | 13.83 | 14.43 | 14.85 | 15.12 | 15.27 | 15.48 | 16.45 | 17.88 | 17.50 | 17.33 | 17.07 | 16.64 |
| 10 | 13.51 | 14.47 | 15.32 | 16.08 | 16.62 | 16.99 | 17.21 | 17.46 | 18.57 | 20.19 | 19.77 | 19.57 | 19.27 | 18.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 19.768 |
| SC2 | 0 | 8 | 13.509 |
| SC3 | -18 | 7 | 11.149 |
| SC4 | -25 | 6 | 8.956 |
| SC5 | -34 | 6 | 8.593 |
| A | 2017 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.