EA-235AG10-C01 C
8.64 kW
Defrost: None
Product code: EA-430AE8-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,260 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 37.1 m² |
| Inner volume | 13.9 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 60 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-430AE8-C05 C | None |
|---|---|
| EA-430AE8-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.36 | 3.35 | 3.35 | 3.37 | 3.37 | 3.35 | 3.32 | 3.41 | 3.64 | 3.95 | 3.88 | 3.85 | 3.82 | 3.76 |
| 5 | 4.38 | 4.41 | 4.46 | 4.50 | 4.52 | 4.50 | 4.46 | 4.54 | 4.83 | 5.24 | 5.10 | 5.05 | 4.99 | 4.90 |
| 6 | 5.37 | 5.47 | 5.58 | 5.67 | 5.71 | 5.71 | 5.67 | 5.74 | 6.09 | 6.60 | 6.39 | 6.32 | 6.21 | 6.04 |
| 7 | 6.36 | 6.54 | 6.69 | 6.85 | 6.93 | 6.96 | 6.92 | 6.99 | 7.41 | 8.02 | 7.76 | 7.66 | 7.51 | 7.25 |
| 8 | 7.26 | 7.54 | 7.80 | 8.03 | 8.17 | 8.21 | 8.19 | 8.27 | 8.76 | 9.48 | 9.19 | 9.06 | 8.87 | 8.55 |
| 9 | 8.11 | 8.48 | 8.84 | 9.16 | 9.36 | 9.47 | 9.48 | 9.57 | 10.14 | 10.97 | 10.64 | 10.49 | 10.26 | 9.88 |
| 10 | 8.85 | 9.34 | 9.79 | 10.18 | 10.46 | 10.59 | 10.66 | 10.80 | 11.46 | 12.42 | 12.11 | 11.94 | 11.68 | 11.24 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 12.107 |
| SC2 | 0 | 8 | 8.270 |
| SC3 | -18 | 7 | 6.889 |
| SC4 | -25 | 6 | 5.575 |
| SC5 | -34 | 6 | 5.401 |
| A | 2107 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 455 mm |
| E2 | 437.5 mm |
| E | 1785 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2107 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.