EA-440AE6-C01 C
23.48 kW
Defrost: None
Product code: EA-445AC8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 21,695 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 59.3 m² |
| Inner volume | 22.7 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 141 kg |
| Quantity | 4 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 1,960 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø42 |
| EA-445AC8-C01 C | None |
|---|---|
| EA-445AC8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.33 | 8.41 | 8.48 | 8.53 | 8.51 | 8.43 | 8.32 | 8.39 | 8.85 | 9.52 | 9.23 | 9.12 | 8.96 | 8.73 |
| 5 | 11.05 | 11.38 | 11.67 | 11.88 | 11.99 | 11.98 | 11.89 | 12.02 | 12.75 | 13.77 | 13.37 | 13.23 | 13.03 | 12.72 |
| 6 | 13.51 | 14.12 | 14.69 | 15.20 | 15.54 | 15.74 | 15.74 | 15.88 | 16.86 | 18.25 | 17.77 | 17.58 | 17.31 | 16.89 |
| 7 | 15.54 | 16.44 | 17.28 | 17.91 | 18.43 | 18.78 | 18.98 | 19.30 | 20.54 | 22.34 | 21.91 | 21.74 | 21.48 | 21.06 |
| 8 | 17.40 | 18.50 | 19.61 | 20.62 | 21.35 | 21.85 | 22.16 | 22.56 | 24.01 | 26.15 | 25.66 | 25.46 | 25.16 | 24.65 |
| 9 | 18.84 | 20.50 | 21.94 | 23.24 | 24.21 | 24.90 | 25.34 | 25.83 | 27.52 | 29.99 | 29.47 | 29.24 | 28.90 | 28.29 |
| 10 | ≈ 20.48 | 22.35 | 24.13 | 25.75 | 27.00 | 27.90 | 28.51 | 29.11 | 31.02 | 33.84 | 33.31 | 33.06 | 32.68 | 31.99 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.312 |
| SC2 | 0 | 8 | 22.558 |
| SC3 | -18 | 7 | 18.144 |
| SC4 | -25 | 6 | 14.687 |
| SC5 | -34 | 6 | 13.655 |
| A | 3167 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E2 | 700 mm |
| E | 2835 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø42 |
| Length | 3167 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.