EA-430AE6-C05 C
9.86 kW
Defrost: None
Product code: EA-530AC6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,624 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 37.4 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 55 kg |
| Quantity | 5 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-530AC6-C05 C | None |
|---|---|
| EA-530AC6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.71 | 3.73 | 3.77 | 3.80 | 3.81 | 3.80 | 3.77 | 3.87 | 4.13 | 4.48 | 4.39 | 4.35 | 4.30 | 4.23 |
| 5 | 4.81 | 4.92 | 5.02 | 5.12 | 5.16 | 5.16 | 5.13 | 5.23 | 5.56 | 6.03 | 5.88 | 5.83 | 5.76 | 5.67 |
| 6 | 5.90 | 6.11 | 6.31 | 6.47 | 6.56 | 6.60 | 6.58 | 6.67 | 7.09 | 7.68 | 7.47 | 7.39 | 7.28 | 7.09 |
| 7 | 6.87 | 7.19 | 7.49 | 7.76 | 7.94 | 8.05 | 8.08 | 8.16 | 8.67 | 9.41 | 9.15 | 9.05 | 8.89 | 8.63 |
| 8 | 7.72 | 8.16 | 8.56 | 8.88 | 9.14 | 9.30 | 9.38 | 9.53 | 10.13 | 11.01 | 10.76 | 10.65 | 10.49 | 10.21 |
| 9 | 8.49 | 9.07 | 9.54 | 10.01 | 10.34 | 10.56 | 10.68 | 10.86 | 11.54 | 12.54 | 12.27 | 12.14 | 11.94 | 11.60 |
| 10 | 9.20 | 9.86 | 10.51 | 11.09 | 11.52 | 11.81 | 11.97 | 12.19 | 12.96 | 14.08 | 13.79 | 13.64 | 13.42 | 13.02 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.785 |
| SC2 | 0 | 8 | 9.526 |
| SC3 | -18 | 7 | 7.840 |
| SC4 | -25 | 6 | 6.305 |
| SC5 | -34 | 6 | 5.954 |
| A | 2407 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 427.5 mm |
| E2 | 410 mm |
| E | 2085 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 2407 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.