EA-440AG8-C01 C
23.36 kW
Defrost: None
Product code: EA-540AC6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 15,895 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 70.1 m² |
| Inner volume | 19.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 127 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-540AC6-C01 C | None |
|---|---|
| EA-540AC6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.48 | 8.67 | 8.84 | 8.99 | 9.03 | 9.01 | 8.95 | 9.10 | 9.66 | 10.43 | 10.16 | 10.05 | 9.91 | 9.69 |
| 5 | 11.02 | 11.49 | 11.91 | 12.26 | 12.46 | 12.51 | 12.49 | 12.67 | 13.47 | 14.59 | 14.21 | 14.09 | 13.91 | 13.62 |
| 6 | 13.17 | 13.90 | 14.56 | 15.07 | 15.48 | 15.75 | 15.90 | 16.18 | 17.22 | 18.74 | 18.38 | 18.24 | 18.04 | 17.66 |
| 7 | 15.04 | 15.92 | 16.89 | 17.73 | 18.33 | 18.73 | 18.98 | 19.32 | 20.57 | 22.39 | 21.97 | 21.80 | 21.54 | 21.10 |
| 8 | 16.73 | 17.95 | 19.18 | 20.30 | 21.12 | 21.70 | 22.06 | 22.49 | 23.94 | 26.09 | 25.62 | 25.42 | 25.09 | 24.52 |
| 9 | ≈ 18.13 | 19.78 | 21.35 | 22.77 | 23.85 | 24.63 | 25.14 | 25.66 | 27.34 | 29.81 | 29.31 | 29.06 | 28.68 | 27.99 |
| 10 | ≈ 19.48 | 21.47 | 23.39 | 25.14 | 26.48 | 27.48 | 28.17 | 28.82 | 30.73 | 33.53 | 33.01 | 32.74 | 32.30 | 31.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 33.011 |
| SC2 | 0 | 8 | 22.485 |
| SC3 | -18 | 7 | 17.993 |
| SC4 | -25 | 6 | 14.562 |
| SC5 | -34 | 6 | 13.340 |
| A | 3117 mm |
|---|---|
| B | 586 mm |
| C | 605 mm |
| F | 395 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 3117 mm |
|---|---|
| Width | 586 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.