EA-463FD10-C19 C
53.56 kW
Defrost: None
Product code: EA-563FC10-C19 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 61,524 m³/h |
|---|---|
| Air throw | 35 m |
| External surface | 203.5 m² |
| Inner volume | 84.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 434 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 68.0 dB(A) |
|---|---|
| Sound power | 91.2 dB(A) |
| Energy class | E |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø66,7 |
| EA-563FC10-C19 C | None |
|---|---|
| EA-563FC10-C19 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 20.22 | 19.91 | 19.73 | 19.64 | 19.48 | 19.30 | 19.10 | 19.06 | 20.14 | 21.72 | 21.13 | 20.92 | 20.61 | 20.16 |
| 5 | 26.99 | 26.82 | 26.84 | 26.90 | 26.80 | 26.59 | 26.33 | 26.26 | 27.77 | 29.93 | 29.07 | 28.75 | 28.29 | 27.58 |
| 6 | 33.55 | 33.90 | 34.25 | 34.58 | 34.64 | 34.49 | 34.25 | 34.17 | 36.14 | 38.96 | 37.80 | 37.36 | 36.74 | 35.79 |
| 7 | 39.79 | 40.74 | 41.60 | 42.34 | 42.58 | 42.67 | 42.55 | 42.52 | 45.00 | 48.55 | 47.15 | 46.61 | 45.83 | 44.58 |
| 8 | 45.64 | 47.06 | 48.53 | 49.82 | 50.60 | 50.98 | 51.05 | 51.16 | 54.18 | 58.57 | 56.99 | 56.36 | 55.43 | 53.93 |
| 9 | 50.47 | 52.68 | 54.72 | 56.58 | 57.86 | 58.71 | 59.23 | 59.73 | 63.43 | 68.80 | 67.08 | 66.39 | 65.35 | 63.64 |
| 10 | 55.09 | 58.02 | 60.71 | 63.11 | 64.81 | 65.96 | 66.70 | 67.34 | 71.55 | 77.71 | 76.19 | 75.56 | 74.60 | 73.00 |
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 18.28 | 17.96 | 17.79 | 17.72 | 17.60 | 17.45 | 17.30 | 17.42 | 18.43 | 19.91 | 19.42 | 19.24 | 18.99 | 18.61 |
| 5 | 24.26 | 24.09 | 24.04 | 24.07 | 23.96 | 23.78 | 23.56 | 23.64 | 25.05 | 27.05 | 26.33 | 26.07 | 25.72 | 25.16 |
| 6 | 30.31 | 30.42 | 30.60 | 30.76 | 30.77 | 30.63 | 30.40 | 30.42 | 32.21 | 34.76 | 33.75 | 33.38 | 32.86 | 32.07 |
| 7 | 36.06 | 36.61 | 37.15 | 37.66 | 37.85 | 37.82 | 37.61 | 37.62 | 39.82 | 42.99 | 41.73 | 41.25 | 40.56 | 39.46 |
| 8 | 41.51 | 42.61 | 43.49 | 44.38 | 44.87 | 45.05 | 44.99 | 45.06 | 47.72 | 51.56 | 50.10 | 49.53 | 48.69 | 47.35 |
| 9 | 46.60 | 48.08 | 49.63 | 51.07 | 51.95 | 52.37 | 52.50 | 52.68 | 55.82 | 60.40 | 58.79 | 58.14 | 57.18 | 55.61 |
| 10 | 50.84 | 53.07 | 55.15 | 57.03 | 58.31 | 59.15 | 59.65 | 60.17 | 63.89 | 69.34 | 67.63 | 66.91 | 65.84 | 64.06 |
| Standard condition | Air inlet [°C] | TD [K] | High speed (Δ) [kW] | Low speed (Y) [kW] |
|---|---|---|---|---|
| SC1 | 10 | 10 | 76.188 | 67.626 |
| SC2 | 0 | 8 | 51.156 | 45.064 |
| SC3 | -18 | 7 | 42.394 | 37.772 |
| SC4 | -25 | 6 | 34.250 | 30.597 |
| SC5 | -34 | 6 | 33.670 | 30.370 |
| A | 5415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 1 x Ø42 |
| D OUT | 1 x Ø66,7 |
| Length | 5415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.