EA-245AC7-C01 C
12.93 kW
Defrost: None
Product code: EA-630BE8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,751 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 46.2 m² |
| Inner volume | 16.3 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 91 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 73.6 dB(A) |
| Energy class | B |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-630BE8-C01 C | None |
|---|---|
| EA-630BE8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.85 | 4.88 | 4.91 | 4.95 | 4.95 | 4.92 | 4.86 | 4.98 | 5.31 | 5.75 | 5.63 | 5.59 | 5.51 | 5.40 |
| 5 | 6.31 | 6.44 | 6.56 | 6.67 | 6.71 | 6.70 | 6.64 | 6.75 | 7.17 | 7.77 | 7.55 | 7.48 | 7.38 | 7.24 |
| 6 | 7.75 | 8.00 | 8.23 | 8.41 | 8.53 | 8.56 | 8.52 | 8.63 | 9.15 | 9.91 | 9.61 | 9.50 | 9.33 | 9.07 |
| 7 | 9.05 | 9.46 | 9.84 | 10.17 | 10.37 | 10.47 | 10.45 | 10.57 | 11.21 | 12.15 | 11.79 | 11.65 | 11.42 | 11.03 |
| 8 | 10.19 | 10.74 | 11.26 | 11.72 | 11.98 | 12.18 | 12.26 | 12.44 | 13.22 | 14.36 | 14.00 | 13.82 | 13.54 | 13.05 |
| 9 | 11.22 | 11.95 | 12.55 | 13.14 | 13.55 | 13.82 | 13.96 | 14.17 | 15.06 | 16.36 | 15.98 | 15.79 | 15.50 | 14.99 |
| 10 | 12.17 | 13.00 | 13.83 | 14.57 | 15.10 | 15.46 | 15.65 | 15.91 | 16.91 | 18.37 | 17.96 | 17.74 | 17.41 | 16.82 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.956 |
| SC2 | 0 | 8 | 12.440 |
| SC3 | -18 | 7 | 10.266 |
| SC4 | -25 | 6 | 8.231 |
| SC5 | -34 | 6 | 7.809 |
| A | 2557 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 2557 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.