EB-130BC4-B05 C
2.34 kW
Defrost: None
Product code: EB-225BA4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,816 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 8.2 m² |
| Inner volume | 1.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 24 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.5 dB(A) |
| Energy class | E |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø12,7 |
| EB-225BA4-B05 C | None |
|---|---|
| EB-225BA4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 0.86 | 0.87 | 0.89 | 0.90 | 0.91 | 0.91 | 0.91 | 0.92 | 0.97 | 1.06 | 1.03 | 1.03 | 1.01 | 1.00 |
| 5 | 1.11 | 1.15 | 1.18 | 1.21 | 1.23 | 1.24 | 1.25 | 1.26 | 1.34 | 1.45 | 1.42 | 1.41 | 1.39 | 1.37 |
| 6 | 1.33 | 1.39 | 1.45 | 1.50 | 1.54 | 1.56 | 1.58 | 1.60 | 1.71 | 1.86 | 1.83 | 1.82 | 1.80 | 1.77 |
| 7 | 1.54 | 1.63 | 1.70 | 1.77 | 1.82 | 1.86 | 1.89 | 1.92 | 2.04 | 2.22 | 2.19 | 2.17 | 2.15 | 2.12 |
| 8 | 1.73 | 1.84 | 1.95 | 2.04 | 2.11 | 2.16 | 2.20 | 2.23 | 2.38 | 2.59 | 2.55 | 2.53 | 2.51 | 2.47 |
| 9 | 1.90 | 2.05 | 2.18 | 2.30 | 2.39 | 2.46 | 2.50 | 2.55 | 2.71 | 2.96 | 2.92 | 2.90 | 2.87 | 2.83 |
| 10 | 2.06 | 2.24 | 2.40 | 2.55 | 2.65 | 2.74 | 2.81 | 2.86 | 3.05 | 3.33 | 3.29 | 3.27 | 3.24 | 3.19 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 3.291 |
| SC2 | 0 | 8 | 2.231 |
| SC3 | -18 | 7 | 1.791 |
| SC4 | -25 | 6 | 1.446 |
| SC5 | -34 | 6 | 1.346 |
| A | 1357 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø12,7 |
| Length | 1357 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.