EB-135AE7-B01 C
4.73 kW
Defrost: None
Product code: EB-230AE4-B05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,858 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 24.7 m² |
| Inner volume | 4.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 32 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 44.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-230AE4-B05 C | None |
|---|---|
| EB-230AE4-B05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.85 | 1.89 | 1.93 | 1.96 | 1.98 | 1.99 | 1.98 | 2.03 | 2.17 | 2.37 | 2.32 | 2.31 | 2.30 | 2.28 |
| 5 | 2.35 | 2.42 | 2.50 | 2.56 | 2.60 | 2.61 | 2.60 | 2.65 | 2.82 | 3.06 | 2.98 | 2.96 | 2.91 | 2.85 |
| 6 | 2.81 | 2.94 | 3.06 | 3.16 | 3.22 | 3.25 | 3.25 | 3.30 | 3.50 | 3.80 | 3.69 | 3.65 | 3.58 | 3.48 |
| 7 | 3.23 | 3.40 | 3.57 | 3.71 | 3.81 | 3.87 | 3.88 | 3.94 | 4.19 | 4.55 | 4.43 | 4.37 | 4.28 | 4.14 |
| 8 | 3.60 | 3.84 | 4.05 | 4.24 | 4.37 | 4.45 | 4.48 | 4.55 | 4.83 | 5.24 | 5.11 | 5.05 | 4.95 | 4.79 |
| 9 | 3.99 | 4.28 | 4.54 | 4.78 | 4.94 | 5.03 | 5.08 | 5.15 | 5.47 | 5.93 | 5.79 | 5.72 | 5.61 | 5.41 |
| 10 | 4.31 | 4.66 | 4.99 | 5.28 | 5.49 | 5.62 | 5.68 | 5.76 | 6.12 | 6.64 | 6.48 | 6.38 | 6.26 | 6.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.475 |
| SC2 | 0 | 8 | 4.545 |
| SC3 | -18 | 7 | 3.756 |
| SC4 | -25 | 6 | 3.055 |
| SC5 | -34 | 6 | 2.839 |
| A | 1197 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1197 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.