EB-330BB6-B05 C
5.19 kW
Defrost: None
Product code: EB-230AE6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,322 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 17.9 m² |
| Inner volume | 4.2 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 68.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EB-230AE6-B01 C | None |
|---|---|
| EB-230AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.99 | 2.03 | 2.08 | 2.12 | 2.14 | 2.14 | 2.13 | 2.19 | 2.33 | 2.53 | 2.48 | 2.46 | 2.44 | 2.41 |
| 5 | 2.52 | 2.62 | 2.71 | 2.79 | 2.84 | 2.85 | 2.85 | 2.90 | 3.08 | 3.35 | 3.26 | 3.23 | 3.18 | 3.11 |
| 6 | 3.02 | 3.17 | 3.31 | 3.44 | 3.53 | 3.58 | 3.59 | 3.65 | 3.87 | 4.21 | 4.09 | 4.05 | 3.98 | 3.87 |
| 7 | 3.45 | 3.66 | 3.86 | 4.03 | 4.15 | 4.23 | 4.26 | 4.33 | 4.61 | 5.01 | 4.89 | 4.84 | 4.77 | 4.63 |
| 8 | 3.88 | 4.15 | 4.40 | 4.63 | 4.77 | 4.87 | 4.93 | 5.01 | 5.32 | 5.79 | 5.66 | 5.60 | 5.50 | 5.34 |
| 9 | 4.24 | 4.59 | 4.91 | 5.19 | 5.39 | 5.53 | 5.60 | 5.69 | 6.05 | 6.57 | 6.42 | 6.35 | 6.24 | 6.04 |
| 10 | ≈ 4.57 | 4.99 | 5.38 | 5.73 | 5.99 | 6.16 | 6.23 | 6.35 | 6.76 | 7.34 | 7.19 | 7.11 | 6.99 | 6.76 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.188 |
| SC2 | 0 | 8 | 5.009 |
| SC3 | -18 | 7 | 4.085 |
| SC4 | -25 | 6 | 3.310 |
| SC5 | -34 | 6 | 3.052 |
| A | 1197 mm |
|---|---|
| B | 523 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1197 mm |
|---|---|
| Width | 523 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.