EB-430BC4-B01 C
9.85 kW
Defrost: None
Product code: EB-240AC6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,916 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 27.7 m² |
| Inner volume | 6.9 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 62 kg |
| Quantity | 2 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 320 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 83.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EB-240AC6-B01 C | None |
|---|---|
| EB-240AC6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.69 | 3.72 | 3.76 | 3.80 | 3.81 | 3.80 | 3.77 | 3.82 | 4.05 | 4.38 | 4.27 | 4.23 | 4.17 | 4.08 |
| 5 | 4.81 | 4.95 | 5.07 | 5.18 | 5.24 | 5.26 | 5.24 | 5.30 | 5.62 | 6.08 | 5.93 | 5.87 | 5.79 | 5.68 |
| 6 | 5.83 | 6.06 | 6.28 | 6.49 | 6.63 | 6.72 | 6.77 | 6.87 | 7.30 | 7.92 | 7.72 | 7.65 | 7.54 | 7.36 |
| 7 | 6.77 | 7.10 | 7.38 | 7.68 | 7.88 | 8.02 | 8.10 | 8.22 | 8.74 | 9.50 | 9.32 | 9.25 | 9.13 | 8.95 |
| 8 | 7.61 | 8.06 | 8.49 | 8.88 | 9.15 | 9.34 | 9.44 | 9.58 | 10.19 | 11.09 | 10.88 | 10.79 | 10.66 | 10.42 |
| 9 | 8.37 | 8.97 | 9.52 | 10.02 | 10.39 | 10.64 | 10.80 | 10.94 | 11.64 | 12.67 | 12.45 | 12.35 | 12.19 | 11.93 |
| 10 | 9.07 | 9.82 | 10.51 | 11.14 | 11.53 | 11.87 | 12.09 | 12.31 | 13.11 | 14.28 | 14.05 | 13.94 | 13.76 | 13.46 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.048 |
| SC2 | 0 | 8 | 9.583 |
| SC3 | -18 | 7 | 7.768 |
| SC4 | -25 | 6 | 6.283 |
| SC5 | -34 | 6 | 5.882 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.