EB-435AC7-B01 C
14.83 kW
Defrost: None
Product code: EB-245AE6-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,991 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 41.6 m² |
| Inner volume | 10.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 80 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EB-245AE6-B01 C | None |
|---|---|
| EB-245AE6-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.55 | 5.45 | 5.39 | 5.36 | 5.31 | 5.24 | 5.17 | 5.30 | 5.61 | 6.06 | 5.91 | 5.86 | 5.78 | 5.68 |
| 5 | 7.50 | 7.46 | 7.45 | 7.45 | 7.40 | 7.30 | 7.19 | 7.30 | 7.76 | 8.38 | 8.15 | 8.08 | 7.98 | 7.85 |
| 6 | 9.45 | 9.52 | 9.61 | 9.68 | 9.67 | 9.59 | 9.44 | 9.54 | 10.11 | 10.91 | 10.54 | 10.41 | 10.24 | 9.99 |
| 7 | 11.28 | 11.50 | 11.73 | 11.96 | 12.03 | 11.99 | 11.86 | 11.94 | 12.63 | 13.63 | 13.15 | 12.97 | 12.71 | 12.30 |
| 8 | 12.87 | 13.23 | 13.58 | 13.91 | 14.11 | 14.19 | 14.17 | 14.32 | 15.19 | 16.47 | 15.95 | 15.72 | 15.38 | 14.83 |
| 9 | 14.48 | 14.98 | 15.46 | 15.85 | 16.13 | 16.27 | 16.27 | 16.43 | 17.42 | 18.88 | 18.36 | 18.14 | 17.81 | 17.23 |
| 10 | 15.92 | 16.61 | 17.25 | 17.82 | 18.17 | 18.34 | 18.39 | 18.57 | 19.69 | 21.33 | 20.76 | 20.50 | 20.10 | 19.39 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.760 |
| SC2 | 0 | 8 | 14.316 |
| SC3 | -18 | 7 | 12.008 |
| SC4 | -25 | 6 | 9.606 |
| SC5 | -34 | 6 | 9.477 |
| A | 1667 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E | 1335 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 1667 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.