EB-445AC7-B01 C
21.23 kW
Defrost: None
Product code: EB-340AE4-B01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,057 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 86.3 m² |
| Inner volume | 15.2 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 101 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | C |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EB-340AE4-B01 C | None |
|---|---|
| EB-340AE4-B01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 8.21 | 8.43 | 8.63 | 8.82 | 8.92 | 8.94 | 8.90 | 9.14 | 9.75 | 10.59 | 10.38 | 10.32 | 10.22 | 10.09 |
| 5 | 10.37 | 10.82 | 11.23 | 11.59 | 11.80 | 11.89 | 11.86 | 12.10 | 12.87 | 13.98 | 13.63 | 13.50 | 13.31 | 13.01 |
| 6 | 12.27 | 12.92 | 13.53 | 14.07 | 14.43 | 14.64 | 14.71 | 14.98 | 15.94 | 17.34 | 16.93 | 16.77 | 16.52 | 16.11 |
| 7 | 14.12 | 15.00 | 15.82 | 16.54 | 16.98 | 17.29 | 17.42 | 17.71 | 18.82 | 20.47 | 19.97 | 19.76 | 19.43 | 18.88 |
| 8 | 15.71 | 16.87 | 17.95 | 18.89 | 19.56 | 19.96 | 20.15 | 20.46 | 21.75 | 23.62 | 23.02 | 22.76 | 22.37 | 21.69 |
| 9 | 17.16 | 18.62 | 19.98 | 21.18 | 22.03 | 22.48 | 22.77 | 23.18 | 24.63 | 26.76 | 26.13 | 25.83 | 25.37 | 24.56 |
| 10 | ≈ 18.46 | 20.23 | 21.90 | 23.17 | 24.28 | 25.03 | 25.44 | 25.92 | 27.56 | 29.94 | 29.29 | 28.95 | 28.43 | 27.48 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 29.287 |
| SC2 | 0 | 8 | 20.463 |
| SC3 | -18 | 7 | 16.705 |
| SC4 | -25 | 6 | 13.529 |
| SC5 | -34 | 6 | 12.424 |
| A | 2317 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E1 | 668 mm |
| E2 | 650 mm |
| E | 1985 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2317 mm |
|---|---|
| Width | 520 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.