EG-325BC7-C23 C
3.41 kW
Defrost: None
Product code: EG-230BC7-C25 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,282 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 9.9 m² |
| Inner volume | 2.7 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EG-230BC7-C25 C | None |
|---|---|
| EG-230BC7-C25 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.28 | 1.27 | 1.27 | 1.27 | 1.27 | 1.26 | 1.25 | 1.28 | 1.36 | 1.47 | 1.44 | 1.42 | 1.41 | 1.38 |
| 5 | 1.69 | 1.70 | 1.72 | 1.74 | 1.74 | 1.73 | 1.72 | 1.74 | 1.85 | 2.01 | 1.95 | 1.94 | 1.91 | 1.88 |
| 6 | 2.09 | 2.13 | 2.18 | 2.22 | 2.24 | 2.24 | 2.23 | 2.25 | 2.39 | 2.58 | 2.51 | 2.48 | 2.44 | 2.37 |
| 7 | 2.46 | 2.54 | 2.62 | 2.69 | 2.74 | 2.76 | 2.75 | 2.78 | 2.95 | 3.20 | 3.10 | 3.07 | 3.01 | 2.92 |
| 8 | 2.79 | 2.90 | 3.01 | 3.11 | 3.18 | 3.23 | 3.24 | 3.29 | 3.49 | 3.79 | 3.71 | 3.67 | 3.60 | 3.49 |
| 9 | 3.12 | 3.27 | 3.41 | 3.53 | 3.62 | 3.68 | 3.71 | 3.76 | 3.99 | 4.34 | 4.24 | 4.19 | 4.12 | 4.00 |
| 10 | 3.41 | 3.61 | 3.79 | 3.95 | 4.06 | 4.14 | 4.17 | 4.23 | 4.50 | 4.89 | 4.78 | 4.72 | 4.64 | 4.51 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 4.776 |
| SC2 | 0 | 8 | 3.286 |
| SC3 | -18 | 7 | 2.715 |
| SC4 | -25 | 6 | 2.175 |
| SC5 | -34 | 6 | 2.097 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.