EG-330AB4-C21 C
5.15 kW
Defrost: None
Product code: EG-230BE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,121 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 23.6 m² |
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 34 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 69.2 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø19 |
| EG-230BE4-C21 C | None |
|---|---|
| EG-230BE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.98 | 2.02 | 2.07 | 2.10 | 2.12 | 2.12 | 2.11 | 2.18 | 2.33 | 2.53 | 2.49 | 2.47 | 2.45 | 2.43 |
| 5 | 2.51 | 2.61 | 2.69 | 2.76 | 2.80 | 2.81 | 2.80 | 2.86 | 3.05 | 3.31 | 3.22 | 3.19 | 3.14 | 3.07 |
| 6 | 3.01 | 3.16 | 3.29 | 3.41 | 3.49 | 3.52 | 3.51 | 3.57 | 3.80 | 4.12 | 4.00 | 3.95 | 3.88 | 3.76 |
| 7 | 3.45 | 3.65 | 3.83 | 4.00 | 4.10 | 4.16 | 4.18 | 4.25 | 4.51 | 4.90 | 4.77 | 4.71 | 4.63 | 4.48 |
| 8 | 3.88 | 4.14 | 4.38 | 4.59 | 4.72 | 4.80 | 4.82 | 4.90 | 5.21 | 5.65 | 5.50 | 5.43 | 5.32 | 5.14 |
| 9 | 4.25 | 4.58 | 4.88 | 5.15 | 5.33 | 5.44 | 5.48 | 5.56 | 5.91 | 6.40 | 6.24 | 6.15 | 6.03 | 5.81 |
| 10 | ≈ 4.59 | 4.99 | 5.37 | 5.70 | 5.93 | 6.07 | 6.11 | 6.22 | 6.60 | 7.15 | 6.97 | 6.88 | 6.73 | 6.48 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.968 |
| SC2 | 0 | 8 | 4.902 |
| SC3 | -18 | 7 | 4.045 |
| SC4 | -25 | 6 | 3.290 |
| SC5 | -34 | 6 | 3.047 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø19 |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |