EG-430AC4-C25 C
8.04 kW
Defrost: None
Product code: EG-235CE4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,651 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 31.0 m² |
| Inner volume | 5.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 37 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EG-235CE4-C21 C | None |
|---|---|
| EG-235CE4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.18 | 3.17 | 3.18 | 3.19 | 3.19 | 3.16 | 3.13 | 3.24 | 3.47 | 3.77 | 3.71 | 3.69 | 3.66 | 3.61 |
| 5 | 4.17 | 4.20 | 4.24 | 4.29 | 4.29 | 4.26 | 4.21 | 4.31 | 4.59 | 4.97 | 4.84 | 4.80 | 4.74 | 4.67 |
| 6 | 5.13 | 5.23 | 5.33 | 5.42 | 5.46 | 5.44 | 5.38 | 5.46 | 5.79 | 6.27 | 6.06 | 5.98 | 5.87 | 5.70 |
| 7 | 5.99 | 6.17 | 6.34 | 6.50 | 6.59 | 6.62 | 6.59 | 6.67 | 7.06 | 7.64 | 7.38 | 7.27 | 7.11 | 6.85 |
| 8 | 6.83 | 7.07 | 7.28 | 7.50 | 7.63 | 7.69 | 7.67 | 7.76 | 8.23 | 8.92 | 8.65 | 8.54 | 8.36 | 8.05 |
| 9 | 7.58 | 7.92 | 8.24 | 8.52 | 8.69 | 8.75 | 8.75 | 8.85 | 9.38 | 10.15 | 9.84 | 9.70 | 9.49 | 9.13 |
| 10 | 8.28 | 8.73 | 9.14 | 9.50 | 9.72 | 9.83 | 9.84 | 9.95 | 10.54 | 11.40 | 11.06 | 10.89 | 10.65 | 10.22 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 11.057 |
| SC2 | 0 | 8 | 7.760 |
| SC3 | -18 | 7 | 6.539 |
| SC4 | -25 | 6 | 5.333 |
| SC5 | -34 | 6 | 5.156 |
| A | 1747 mm |
|---|---|
| B | 685 mm |
| C | 355 mm |
| F | 630 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1747 mm |
|---|---|
| Width | 685 mm |
| Height | 355 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.