EG-330BC7-C25 C
5.18 kW
Defrost: None
Product code: EG-330AB4-C21 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 3,919 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 17.6 m² |
| Inner volume | 2.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 46 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.0 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø19 |
| EG-330AB4-C21 C | None |
|---|---|
| EG-330AB4-C21 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.92 | 1.95 | 1.97 | 1.99 | 2.00 | 1.99 | 1.97 | 2.01 | 2.13 | 2.30 | 2.24 | 2.22 | 2.19 | 2.15 |
| 5 | 2.50 | 2.58 | 2.66 | 2.73 | 2.77 | 2.79 | 2.77 | 2.81 | 2.99 | 3.23 | 3.15 | 3.12 | 3.08 | 3.03 |
| 6 | 3.01 | 3.12 | 3.24 | 3.35 | 3.42 | 3.46 | 3.48 | 3.54 | 3.77 | 4.09 | 4.01 | 3.98 | 3.94 | 3.87 |
| 7 | 3.47 | 3.66 | 3.83 | 3.99 | 4.09 | 4.15 | 4.18 | 4.24 | 4.51 | 4.91 | 4.80 | 4.76 | 4.70 | 4.60 |
| 8 | 3.90 | 4.16 | 4.39 | 4.60 | 4.75 | 4.84 | 4.88 | 4.95 | 5.27 | 5.72 | 5.61 | 5.56 | 5.49 | 5.37 |
| 9 | 4.28 | 4.62 | 4.93 | 5.17 | 5.37 | 5.50 | 5.58 | 5.67 | 6.04 | 6.57 | 6.44 | 6.38 | 6.30 | 6.15 |
| 10 | ≈ 4.63 | 5.05 | 5.40 | 5.74 | 5.99 | 6.17 | 6.28 | 6.40 | 6.81 | 7.41 | 7.28 | 7.22 | 7.12 | 6.96 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.279 |
| SC2 | 0 | 8 | 4.952 |
| SC3 | -18 | 7 | 4.033 |
| SC4 | -25 | 6 | 3.243 |
| SC5 | -34 | 6 | 3.044 |
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø19 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.