EA-330AE10-C01 C
6.91 kW
Defrost: None
Product code: EA-145AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 5,040 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 18.3 m² |
| Inner volume | 8.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 53 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-145AE10-C01 C | None |
|---|---|
| EA-145AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.53 | 2.47 | 2.44 | 2.41 | 2.38 | 2.35 | 2.31 | 2.34 | 2.47 | 2.66 | 2.58 | 2.56 | 2.52 | 2.47 |
| 5 | 3.44 | 3.41 | 3.39 | 3.38 | 3.35 | 3.31 | 3.25 | 3.28 | 3.48 | 3.75 | 3.64 | 3.60 | 3.55 | 3.46 |
| 6 | 4.35 | 4.37 | 4.40 | 4.42 | 4.41 | 4.37 | 4.30 | 4.33 | 4.58 | 4.94 | 4.77 | 4.71 | 4.63 | 4.52 |
| 7 | 5.26 | 5.32 | 5.41 | 5.49 | 5.51 | 5.49 | 5.43 | 5.45 | 5.77 | 6.22 | 6.00 | 5.92 | 5.81 | 5.63 |
| 8 | 6.09 | 6.27 | 6.43 | 6.57 | 6.63 | 6.64 | 6.60 | 6.63 | 7.01 | 7.57 | 7.31 | 7.21 | 7.06 | 6.82 |
| 9 | 6.87 | 7.13 | 7.37 | 7.59 | 7.74 | 7.81 | 7.79 | 7.83 | 8.29 | 8.96 | 8.68 | 8.56 | 8.38 | 8.08 |
| 10 | 7.55 | 7.89 | 8.22 | 8.51 | 8.70 | 8.80 | 8.86 | 8.96 | 9.51 | 10.32 | 10.06 | 9.92 | 9.72 | 9.38 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.055 |
| SC2 | 0 | 8 | 6.627 |
| SC3 | -18 | 7 | 5.500 |
| SC4 | -25 | 6 | 4.395 |
| SC5 | -34 | 6 | 4.359 |
| A | 1067 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E | 735 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1067 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.