EA-430AE6-C05 C
9.86 kW
Defrost: None
Product code: EA-145AG6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 4,176 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 38.4 m² |
| Inner volume | 11.5 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 66 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 490 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø28 |
| EA-145AG6-C01 C | None |
|---|---|
| EA-145AG6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.74 | 3.82 | 3.89 | 3.96 | 3.98 | 3.97 | 3.92 | 4.06 | 4.33 | 4.71 | 4.62 | 4.59 | 4.56 | 4.50 |
| 5 | 4.77 | 4.95 | 5.11 | 5.24 | 5.31 | 5.31 | 5.26 | 5.40 | 5.74 | 6.23 | 6.06 | 6.00 | 5.92 | 5.80 |
| 6 | 5.77 | 6.06 | 6.33 | 6.55 | 6.66 | 6.70 | 6.66 | 6.78 | 7.20 | 7.81 | 7.56 | 7.46 | 7.31 | 7.07 |
| 7 | 6.65 | 7.07 | 7.44 | 7.77 | 7.98 | 8.09 | 8.10 | 8.20 | 8.69 | 9.43 | 9.12 | 8.99 | 8.79 | 8.45 |
| 8 | 7.41 | 7.95 | 8.45 | 8.83 | 9.13 | 9.29 | 9.34 | 9.50 | 10.09 | 10.95 | 10.65 | 10.50 | 10.28 | 9.86 |
| 9 | 8.09 | 8.78 | 9.34 | 9.89 | 10.27 | 10.51 | 10.60 | 10.78 | 11.45 | 12.42 | 12.08 | 11.92 | 11.65 | 11.17 |
| 10 | ≈ 8.71 | 9.47 | 10.23 | 10.91 | 11.39 | 11.71 | 11.85 | 12.07 | 12.81 | 13.89 | 13.53 | 13.34 | 13.03 | 12.47 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.531 |
| SC2 | 0 | 8 | 9.504 |
| SC3 | -18 | 7 | 7.867 |
| SC4 | -25 | 6 | 6.327 |
| SC5 | -34 | 6 | 5.840 |
| A | 1067 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E | 735 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø28 |
| Length | 1067 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.