EA-630BC8-C01 C
10.18 kW
Defrost: None
Product code: EA-150AE8-C09 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,504 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 28.8 m² |
| Inner volume | 11.1 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 65 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 710 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-150AE8-C09 C | None |
|---|---|
| EA-150AE8-C09 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.67 | 3.63 | 3.60 | 3.59 | 3.56 | 3.51 | 3.46 | 3.51 | 3.71 | 4.00 | 3.89 | 3.85 | 3.80 | 3.71 |
| 5 | 4.92 | 4.94 | 4.96 | 4.99 | 4.97 | 4.92 | 4.85 | 4.90 | 5.20 | 5.61 | 5.45 | 5.39 | 5.32 | 5.20 |
| 6 | 6.14 | 6.25 | 6.36 | 6.46 | 6.48 | 6.45 | 6.39 | 6.43 | 6.81 | 7.35 | 7.12 | 7.03 | 6.92 | 6.74 |
| 7 | 7.33 | 7.57 | 7.78 | 7.96 | 8.05 | 8.05 | 8.01 | 8.06 | 8.53 | 9.22 | 8.91 | 8.80 | 8.63 | 8.37 |
| 8 | 8.39 | 8.74 | 9.06 | 9.36 | 9.55 | 9.66 | 9.68 | 9.72 | 10.30 | 11.15 | 10.81 | 10.67 | 10.47 | 10.13 |
| 9 | 9.30 | 9.79 | 10.23 | 10.58 | 10.85 | 11.02 | 11.10 | 11.23 | 11.93 | 12.95 | 12.65 | 12.52 | 12.33 | 11.96 |
| 10 | 10.15 | 10.78 | 11.30 | 11.81 | 12.16 | 12.39 | 12.51 | 12.68 | 13.47 | 14.62 | 14.30 | 14.15 | 13.93 | 13.55 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 14.297 |
| SC2 | 0 | 8 | 9.721 |
| SC3 | -18 | 7 | 8.006 |
| SC4 | -25 | 6 | 6.363 |
| SC5 | -34 | 6 | 6.169 |
| A | 1237 mm |
|---|---|
| B | 640 mm |
| C | 685 mm |
| F | 445 mm |
| E | 885 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1237 mm |
|---|---|
| Width | 640 mm |
| Height | 685 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.