EA-630BC10-C01 C
9.62 kW
Defrost: None
Product code: EA-163ED10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,664 m³/h |
|---|---|
| Air throw | 21 m |
| External surface | 40.5 m² |
| Inner volume | 16.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 112 kg |
| Quantity | 1 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 74.3 dB(A) |
| Energy class | C |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø28 |
| EA-163ED10-C01 C | None |
|---|---|
| EA-163ED10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.67 | 3.63 | 3.60 | 3.59 | 3.57 | 3.54 | 3.50 | 3.54 | 3.74 | 4.04 | 3.94 | 3.90 | 3.85 | 3.77 |
| 5 | 4.86 | 4.86 | 4.87 | 4.89 | 4.87 | 4.83 | 4.78 | 4.81 | 5.10 | 5.50 | 5.36 | 5.30 | 5.23 | 5.12 |
| 6 | 6.05 | 6.13 | 6.20 | 6.26 | 6.26 | 6.24 | 6.18 | 6.20 | 6.57 | 7.09 | 6.87 | 6.80 | 6.69 | 6.52 |
| 7 | 7.17 | 7.35 | 7.52 | 7.65 | 7.71 | 7.71 | 7.66 | 7.68 | 8.13 | 8.77 | 8.50 | 8.40 | 8.25 | 8.02 |
| 8 | 8.21 | 8.53 | 8.76 | 9.00 | 9.13 | 9.18 | 9.16 | 9.20 | 9.74 | 10.52 | 10.20 | 10.08 | 9.89 | 9.60 |
| 9 | 9.18 | 9.58 | 9.97 | 10.32 | 10.56 | 10.67 | 10.69 | 10.75 | 11.39 | 12.33 | 11.97 | 11.83 | 11.62 | 11.26 |
| 10 | 9.97 | 10.53 | 11.05 | 11.50 | 11.82 | 12.01 | 12.12 | 12.25 | 13.00 | 14.11 | 13.77 | 13.61 | 13.37 | 12.96 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 13.771 |
| SC2 | 0 | 8 | 9.197 |
| SC3 | -18 | 7 | 7.684 |
| SC4 | -25 | 6 | 6.197 |
| SC5 | -34 | 6 | 6.075 |
| A | 1215 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E | 835 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø28 |
| Length | 1215 mm |
|---|---|
| Width | 1000 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.