EA-230AE8-C01 C
4.64 kW
Defrost: None
Product code: EA-230AE6-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 1,909 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 21.9 m² |
| Inner volume | 6.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230AE6-C05 C | None |
|---|---|
| EA-230AE6-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.83 | 1.83 | 1.85 | 1.87 | 1.87 | 1.87 | 1.85 | 1.91 | 2.04 | 2.22 | 2.19 | 2.17 | 2.16 | 2.14 |
| 5 | 2.35 | 2.38 | 2.42 | 2.46 | 2.48 | 2.47 | 2.45 | 2.50 | 2.66 | 2.89 | 2.81 | 2.79 | 2.75 | 2.70 |
| 6 | 2.84 | 2.92 | 3.00 | 3.06 | 3.10 | 3.10 | 3.09 | 3.13 | 3.32 | 3.60 | 3.49 | 3.45 | 3.39 | 3.29 |
| 7 | 3.34 | 3.46 | 3.58 | 3.67 | 3.73 | 3.75 | 3.73 | 3.77 | 4.00 | 4.33 | 4.20 | 4.14 | 4.06 | 3.93 |
| 8 | 3.78 | 3.96 | 4.13 | 4.28 | 4.36 | 4.40 | 4.39 | 4.43 | 4.70 | 5.08 | 4.93 | 4.87 | 4.77 | 4.59 |
| 9 | 4.19 | 4.42 | 4.64 | 4.83 | 4.95 | 5.02 | 5.03 | 5.09 | 5.40 | 5.84 | 5.67 | 5.60 | 5.48 | 5.27 |
| 10 | 4.55 | 4.85 | 5.12 | 5.33 | 5.49 | 5.59 | 5.63 | 5.70 | 6.05 | 6.56 | 6.40 | 6.32 | 6.19 | 5.96 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 6.396 |
| SC2 | 0 | 8 | 4.432 |
| SC3 | -18 | 7 | 3.697 |
| SC4 | -25 | 6 | 2.997 |
| SC5 | -34 | 6 | 2.864 |
| A | 1157 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 417.5 mm |
| E | 835 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1157 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.