EA-330AC6-C05 C
6.24 kW
Defrost: None
Product code: EA-230BE4-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,376 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 38.0 m² |
| Inner volume | 7.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 47 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 124 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 46.0 dB(A) |
|---|---|
| Sound power | 68.0 dB(A) |
| Energy class | B |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230BE4-C01 C | None |
|---|---|
| EA-230BE4-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.37 | 2.45 | 2.52 | 2.58 | 2.62 | 2.64 | 2.63 | 2.70 | 2.88 | 3.13 | 3.07 | 3.06 | 3.03 | 3.00 |
| 5 | 2.96 | 3.11 | 3.24 | 3.35 | 3.42 | 3.45 | 3.45 | 3.52 | 3.74 | 4.07 | 3.97 | 3.93 | 3.88 | 3.79 |
| 6 | 3.54 | 3.75 | 3.95 | 4.12 | 4.23 | 4.28 | 4.30 | 4.37 | 4.64 | 5.04 | 4.91 | 4.85 | 4.77 | 4.63 |
| 7 | 4.04 | 4.33 | 4.59 | 4.82 | 4.99 | 5.07 | 5.12 | 5.21 | 5.53 | 6.02 | 5.86 | 5.80 | 5.69 | 5.51 |
| 8 | 4.47 | 4.84 | 5.18 | 5.44 | 5.66 | 5.81 | 5.88 | 5.99 | 6.37 | 6.92 | 6.76 | 6.69 | 6.58 | 6.38 |
| 9 | ≈ 4.86 | 5.31 | 5.69 | 6.07 | 6.35 | 6.54 | 6.65 | 6.77 | 7.20 | 7.82 | 7.66 | 7.57 | 7.44 | 7.20 |
| 10 | 5.20 | 5.70 | 6.20 | 6.66 | 7.01 | 7.26 | 7.40 | 7.55 | 8.03 | 8.73 | 8.55 | 8.46 | 8.31 | 8.04 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 8.552 |
| SC2 | 0 | 8 | 5.987 |
| SC3 | -18 | 7 | 4.896 |
| SC4 | -25 | 6 | 3.948 |
| SC5 | -34 | 6 | 3.590 |
| A | 1357 mm |
|---|---|
| B | 573 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 573 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.