EA-140AE7-C01 C
5.45 kW
Defrost: None
Product code: EA-230BE4-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,040 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 38.0 m² |
| Inner volume | 7.9 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 40 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø22 |
| EA-230BE4-C05 C | None |
|---|---|
| EA-230BE4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 2.17 | 2.23 | 2.28 | 2.33 | 2.36 | 2.37 | 2.36 | 2.43 | 2.60 | 2.83 | 2.78 | 2.76 | 2.74 | 2.72 |
| 5 | 2.72 | 2.83 | 2.93 | 3.01 | 3.06 | 3.08 | 3.07 | 3.14 | 3.34 | 3.63 | 3.53 | 3.50 | 3.45 | 3.37 |
| 6 | 3.26 | 3.43 | 3.58 | 3.69 | 3.78 | 3.82 | 3.81 | 3.87 | 4.11 | 4.47 | 4.33 | 4.28 | 4.20 | 4.06 |
| 7 | 3.74 | 3.97 | 4.19 | 4.38 | 4.50 | 4.56 | 4.56 | 4.62 | 4.91 | 5.32 | 5.15 | 5.09 | 4.98 | 4.80 |
| 8 | 4.16 | 4.46 | 4.74 | 4.99 | 5.13 | 5.23 | 5.26 | 5.35 | 5.68 | 6.16 | 5.99 | 5.91 | 5.78 | 5.57 |
| 9 | ≈ 4.54 | 4.92 | 5.27 | 5.54 | 5.76 | 5.89 | 5.95 | 6.04 | 6.42 | 6.96 | 6.78 | 6.69 | 6.56 | 6.33 |
| 10 | ≈ 4.88 | 5.34 | 5.72 | 6.09 | 6.36 | 6.54 | 6.63 | 6.74 | 7.16 | 7.76 | 7.57 | 7.47 | 7.32 | 7.06 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 7.569 |
| SC2 | 0 | 8 | 5.347 |
| SC3 | -18 | 7 | 4.431 |
| SC4 | -25 | 6 | 3.576 |
| SC5 | -34 | 6 | 3.300 |
| A | 1357 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E | 1035 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø22 |
| Length | 1357 mm |
|---|---|
| Width | 567 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.