EA-150AE7-C10 C
11.03 kW
Defrost: None
Product code: EA-245AC10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 11,107 m³/h |
|---|---|
| Air throw | 18 m |
| External surface | 24.4 m² |
| Inner volume | 11.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 77 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-245AC10-C01 C | None |
|---|---|
| EA-245AC10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.87 | 3.82 | 3.78 | 3.75 | 3.70 | 3.64 | 3.58 | 3.58 | 3.77 | 4.05 | 3.92 | 3.87 | 3.80 | 3.70 |
| 5 | 5.24 | 5.26 | 5.29 | 5.31 | 5.29 | 5.23 | 5.15 | 5.17 | 5.47 | 5.88 | 5.70 | 5.62 | 5.52 | 5.36 |
| 6 | 6.61 | 6.74 | 6.84 | 6.95 | 6.98 | 6.97 | 6.91 | 6.93 | 7.34 | 7.91 | 7.65 | 7.56 | 7.43 | 7.23 |
| 7 | 7.87 | 8.14 | 8.39 | 8.61 | 8.73 | 8.78 | 8.75 | 8.80 | 9.32 | 10.07 | 9.77 | 9.65 | 9.48 | 9.21 |
| 8 | 8.95 | 9.34 | 9.70 | 10.04 | 10.23 | 10.39 | 10.47 | 10.60 | 11.27 | 12.25 | 11.97 | 11.84 | 11.64 | 11.32 |
| 9 | 9.93 | 10.47 | 10.91 | 11.36 | 11.68 | 11.89 | 12.03 | 12.19 | 12.96 | 14.09 | 13.81 | 13.69 | 13.51 | 13.21 |
| 10 | 10.84 | 11.48 | 12.11 | 12.68 | 13.10 | 13.39 | 13.58 | 13.79 | 14.67 | 15.96 | 15.65 | 15.52 | 15.32 | 14.98 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 15.654 |
| SC2 | 0 | 8 | 10.602 |
| SC3 | -18 | 7 | 8.668 |
| SC4 | -25 | 6 | 6.838 |
| SC5 | -34 | 6 | 6.647 |
| A | 1767 mm |
|---|---|
| B | 590 mm |
| C | 645 mm |
| F | 395 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1767 mm |
|---|---|
| Width | 590 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.