EA-340AE4-C01 C
17.69 kW
Defrost: None
Product code: EA-245AE6-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,305 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 57.5 m² |
| Inner volume | 17.0 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 93 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-245AE6-C01 C | None |
|---|---|
| EA-245AE6-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.62 | 6.62 | 6.64 | 6.66 | 6.64 | 6.59 | 6.51 | 6.68 | 7.11 | 7.68 | 7.50 | 7.43 | 7.34 | 7.19 |
| 5 | 8.69 | 8.84 | 8.97 | 9.08 | 9.11 | 9.06 | 8.96 | 9.12 | 9.69 | 10.49 | 10.21 | 10.12 | 9.99 | 9.82 |
| 6 | 10.75 | 11.07 | 11.36 | 11.61 | 11.70 | 11.70 | 11.61 | 11.75 | 12.47 | 13.48 | 13.06 | 12.91 | 12.69 | 12.36 |
| 7 | 12.57 | 13.08 | 13.56 | 13.99 | 14.26 | 14.40 | 14.37 | 14.49 | 15.36 | 16.64 | 16.12 | 15.92 | 15.62 | 15.13 |
| 8 | 14.15 | 14.88 | 15.55 | 16.07 | 16.46 | 16.69 | 16.77 | 17.00 | 18.05 | 19.60 | 19.11 | 18.90 | 18.59 | 18.06 |
| 9 | 15.61 | 16.49 | 17.37 | 18.15 | 18.69 | 19.00 | 19.14 | 19.41 | 20.61 | 22.37 | 21.83 | 21.58 | 21.22 | 20.59 |
| 10 | 16.94 | 18.07 | 19.19 | 20.18 | 20.86 | 21.30 | 21.51 | 21.84 | 23.19 | 25.17 | 24.58 | 24.30 | 23.88 | 23.15 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 24.582 |
| SC2 | 0 | 8 | 16.996 |
| SC3 | -18 | 7 | 14.116 |
| SC4 | -25 | 6 | 11.360 |
| SC5 | -34 | 6 | 10.830 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.