EA-163GC7-C08 C
16.90 kW
Defrost: None
Product code: EA-245AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,526 m³/h |
|---|---|
| Air throw | 16 m |
| External surface | 50.1 m² |
| Inner volume | 17.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 92 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-245AE7-C01 C | None |
|---|---|
| EA-245AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 6.23 | 6.20 | 6.19 | 6.19 | 6.15 | 6.09 | 6.00 | 6.15 | 6.51 | 7.03 | 6.85 | 6.78 | 6.68 | 6.54 |
| 5 | 8.26 | 8.36 | 8.45 | 8.52 | 8.52 | 8.46 | 8.34 | 8.47 | 9.00 | 9.73 | 9.45 | 9.37 | 9.24 | 9.06 |
| 6 | 10.28 | 10.53 | 10.77 | 10.94 | 11.02 | 11.00 | 10.89 | 11.01 | 11.67 | 12.61 | 12.20 | 12.05 | 11.85 | 11.53 |
| 7 | 12.12 | 12.57 | 12.99 | 13.37 | 13.58 | 13.63 | 13.55 | 13.67 | 14.49 | 15.67 | 15.16 | 14.96 | 14.67 | 14.19 |
| 8 | 13.68 | 14.33 | 14.93 | 15.46 | 15.74 | 15.94 | 16.00 | 16.21 | 17.21 | 18.69 | 18.21 | 17.99 | 17.63 | 17.04 |
| 9 | 15.13 | 16.01 | 16.72 | 17.42 | 17.90 | 18.17 | 18.30 | 18.54 | 19.69 | 21.37 | 20.84 | 20.61 | 20.26 | 19.66 |
| 10 | 16.46 | 17.49 | 18.50 | 19.39 | 20.01 | 20.40 | 20.59 | 20.89 | 22.18 | 24.07 | 23.51 | 23.24 | 22.84 | 22.14 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 23.505 |
| SC2 | 0 | 8 | 16.209 |
| SC3 | -18 | 7 | 13.478 |
| SC4 | -25 | 6 | 10.766 |
| SC5 | -34 | 6 | 10.346 |
| A | 1767 mm |
|---|---|
| B | 640 mm |
| C | 645 mm |
| F | 445 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1767 mm |
|---|---|
| Width | 640 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.