EA-440AE10-C01 C
19.57 kW
Defrost: None
Product code: EA-245AG7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 8,625 m³/h |
|---|---|
| Air throw | 15 m |
| External surface | 66.8 m² |
| Inner volume | 22.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 112 kg |
| Quantity | 2 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,310 rpm |
| Power | 980 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 78.0 dB(A) |
| Energy class | D |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø42 |
| EA-245AG7-C01 C | None |
|---|---|
| EA-245AG7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 7.60 | 7.56 | 7.55 | 7.56 | 7.53 | 7.47 | 7.37 | 7.58 | 8.08 | 8.76 | 8.59 | 8.53 | 8.43 | 8.27 |
| 5 | 9.96 | 10.03 | 10.11 | 10.20 | 10.19 | 10.12 | 9.98 | 10.17 | 10.80 | 11.69 | 11.36 | 11.25 | 11.10 | 10.90 |
| 6 | 12.25 | 12.48 | 12.71 | 12.91 | 12.98 | 12.94 | 12.78 | 12.93 | 13.71 | 14.82 | 14.33 | 14.14 | 13.87 | 13.44 |
| 7 | 14.50 | 14.92 | 15.32 | 15.67 | 15.81 | 15.83 | 15.69 | 15.83 | 16.76 | 18.11 | 17.44 | 17.17 | 16.77 | 16.12 |
| 8 | 16.51 | 17.15 | 17.76 | 18.30 | 18.63 | 18.75 | 18.64 | 18.79 | 19.88 | 21.47 | 20.70 | 20.36 | 19.85 | 18.99 |
| 9 | 18.29 | 19.17 | 19.98 | 20.70 | 21.07 | 21.32 | 21.35 | 21.59 | 22.88 | 24.76 | 23.98 | 23.58 | 22.98 | 21.92 |
| 10 | 19.95 | 21.09 | 22.03 | 22.95 | 23.54 | 23.89 | 23.98 | 24.26 | 25.70 | 27.79 | 26.98 | 26.58 | 25.97 | 24.86 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 26.975 |
| SC2 | 0 | 8 | 18.786 |
| SC3 | -18 | 7 | 15.752 |
| SC4 | -25 | 6 | 12.708 |
| SC5 | -34 | 6 | 12.311 |
| A | 1767 mm |
|---|---|
| B | 690 mm |
| C | 645 mm |
| F | 495 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø42 |
| Length | 1767 mm |
|---|---|
| Width | 690 mm |
| Height | 645 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.