EA-150AC8-C09 C
7.56 kW
Defrost: None
Product code: EA-330AE4-C05 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 2,803 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 49.5 m² |
| Inner volume | 10.4 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 49 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 45.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | D |
| Inlet | Ø12,7 |
|---|---|
| Outlet | Ø28 |
| EA-330AE4-C05 C | None |
|---|---|
| EA-330AE4-C05 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 3.10 | 3.11 | 3.14 | 3.17 | 3.19 | 3.18 | 3.16 | 3.26 | 3.48 | 3.79 | 3.73 | 3.71 | 3.68 | 3.65 |
| 5 | 3.96 | 4.01 | 4.07 | 4.13 | 4.16 | 4.16 | 4.13 | 4.20 | 4.47 | 4.85 | 4.73 | 4.69 | 4.62 | 4.53 |
| 6 | 4.79 | 4.90 | 5.01 | 5.11 | 5.16 | 5.17 | 5.14 | 5.20 | 5.52 | 5.98 | 5.80 | 5.73 | 5.63 | 5.46 |
| 7 | 5.62 | 5.79 | 5.96 | 6.09 | 6.18 | 6.20 | 6.17 | 6.23 | 6.60 | 7.15 | 6.93 | 6.83 | 6.69 | 6.46 |
| 8 | 6.36 | 6.63 | 6.87 | 7.08 | 7.21 | 7.25 | 7.23 | 7.29 | 7.72 | 8.35 | 8.09 | 7.97 | 7.80 | 7.50 |
| 9 | 7.05 | 7.39 | 7.72 | 8.00 | 8.18 | 8.27 | 8.29 | 8.35 | 8.84 | 9.55 | 9.26 | 9.13 | 8.92 | 8.57 |
| 10 | 7.66 | 8.11 | 8.52 | 8.84 | 9.07 | 9.21 | 9.25 | 9.35 | 9.91 | 10.72 | 10.43 | 10.29 | 10.06 | 9.65 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 10.433 |
| SC2 | 0 | 8 | 7.289 |
| SC3 | -18 | 7 | 6.134 |
| SC4 | -25 | 6 | 5.008 |
| SC5 | -34 | 6 | 4.820 |
| A | 1657 mm |
|---|---|
| B | 567 mm |
| C | 445 mm |
| F | 395 mm |
| E1 | 450.5 mm |
| E2 | 434 mm |
| E | 1335 mm |
| D IN | 1 x Ø12,7 |
| D OUT | 1 x Ø28 |
| Length | 1657 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.