EA-150AE4-C10 C
12.67 kW
Defrost: None
Product code: EA-335AE7-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,494 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 42.9 m² |
| Inner volume | 14.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 78 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | C |
| Inlet | Ø15,9 |
|---|---|
| Outlet | Ø28 |
| EA-335AE7-C01 C | None |
|---|---|
| EA-335AE7-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 4.74 | 4.83 | 4.91 | 4.98 | 5.01 | 4.99 | 4.95 | 5.08 | 5.42 | 5.88 | 5.76 | 5.72 | 5.65 | 5.54 |
| 5 | 6.09 | 6.31 | 6.51 | 6.68 | 6.76 | 6.78 | 6.74 | 6.87 | 7.31 | 7.92 | 7.71 | 7.64 | 7.54 | 7.39 |
| 6 | 7.40 | 7.77 | 8.10 | 8.39 | 8.57 | 8.64 | 8.62 | 8.76 | 9.30 | 10.08 | 9.80 | 9.69 | 9.52 | 9.25 |
| 7 | 8.51 | 9.03 | 9.50 | 9.92 | 10.16 | 10.34 | 10.42 | 10.60 | 11.27 | 12.26 | 11.96 | 11.82 | 11.61 | 11.25 |
| 8 | 9.49 | 10.18 | 10.74 | 11.29 | 11.69 | 11.94 | 12.07 | 12.28 | 13.06 | 14.20 | 13.88 | 13.74 | 13.52 | 13.13 |
| 9 | 10.38 | 11.17 | 11.96 | 12.67 | 13.18 | 13.52 | 13.71 | 13.97 | 14.86 | 16.15 | 15.81 | 15.64 | 15.38 | 14.93 |
| 10 | ≈ 11.18 | 12.14 | 13.11 | 13.98 | 14.63 | 15.08 | 15.34 | 15.66 | 16.66 | 18.12 | 17.75 | 17.57 | 17.27 | 16.75 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 17.750 |
| SC2 | 0 | 8 | 12.279 |
| SC3 | -18 | 7 | 10.051 |
| SC4 | -25 | 6 | 8.104 |
| SC5 | -34 | 6 | 7.485 |
| A | 1857 mm |
|---|---|
| B | 573 mm |
| C | 525 mm |
| F | 395 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø15,9 |
| D OUT | 1 x Ø28 |
| Length | 1857 mm |
|---|---|
| Width | 573 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.