EA-530AE4-C01 C
13.60 kW
Defrost: None
Product code: EA-335AG8-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 6,029 m³/h |
|---|---|
| Air throw | 10 m |
| External surface | 50.8 m² |
| Inner volume | 19.2 dm³ |
| Fin spacing | 8.0 mm |
| Fin material | Aluminium |
| Net weight | 96 kg |
| Quantity | 3 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 495 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 53.0 dB(A) |
|---|---|
| Sound power | 75.0 dB(A) |
| Energy class | B |
| Inlet | Ø19 |
|---|---|
| Outlet | Ø35 |
| EA-335AG8-C01 C | None |
|---|---|
| EA-335AG8-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.23 | 5.25 | 5.30 | 5.34 | 5.35 | 5.32 | 5.27 | 5.41 | 5.77 | 6.27 | 6.14 | 6.10 | 6.05 | 5.96 |
| 5 | 6.74 | 6.87 | 7.00 | 7.12 | 7.17 | 7.15 | 7.09 | 7.22 | 7.67 | 8.32 | 8.08 | 8.00 | 7.89 | 7.73 |
| 6 | 8.19 | 8.45 | 8.70 | 8.92 | 9.03 | 9.06 | 9.00 | 9.12 | 9.67 | 10.48 | 10.15 | 10.02 | 9.83 | 9.52 |
| 7 | 9.60 | 10.02 | 10.40 | 10.73 | 10.92 | 10.99 | 10.96 | 11.08 | 11.75 | 12.72 | 12.31 | 12.14 | 11.88 | 11.45 |
| 8 | 10.85 | 11.42 | 11.95 | 12.42 | 12.73 | 12.90 | 12.93 | 13.05 | 13.83 | 14.98 | 14.51 | 14.31 | 13.99 | 13.45 |
| 9 | 11.95 | 12.70 | 13.39 | 14.00 | 14.33 | 14.59 | 14.69 | 14.90 | 15.82 | 17.14 | 16.70 | 16.47 | 16.14 | 15.49 |
| 10 | 12.96 | 13.90 | 14.68 | 15.43 | 15.96 | 16.29 | 16.45 | 16.70 | 17.73 | 19.21 | 18.72 | 18.48 | 18.10 | 17.43 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 18.721 |
| SC2 | 0 | 8 | 13.045 |
| SC3 | -18 | 7 | 10.821 |
| SC4 | -25 | 6 | 8.701 |
| SC5 | -34 | 6 | 8.252 |
| A | 1857 mm |
|---|---|
| B | 673 mm |
| C | 525 mm |
| F | 495 mm |
| E1 | 517.5 mm |
| E2 | 500 mm |
| E | 1535 mm |
| D IN | 1 x Ø19 |
| D OUT | 1 x Ø35 |
| Length | 1857 mm |
|---|---|
| Width | 623 mm |
| Height | 525 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.