EA-335AG4-C01 C
14.69 kW
Defrost: None
Product code: EA-340AE10-C01 C
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
How to read the code of this model.
| Air flow | 9,121 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 40.3 m² |
| Inner volume | 18.6 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 95 kg |
| Quantity | 3 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 480 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | B |
| Inlet | Ø22 |
|---|---|
| Outlet | Ø35 |
| EA-340AE10-C01 C | None |
|---|---|
| EA-340AE10-C01 C ED | Electric |
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R404A, dew point -8 °C, air inlet 0 °C (TD 8 K)
R404A, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 5.34 | 5.44 | 5.53 | 5.61 | 5.63 | 5.62 | 5.56 | 5.69 | 6.05 | 6.55 | 6.38 | 6.32 | 6.23 | 6.09 |
| 5 | 6.87 | 7.12 | 7.36 | 7.55 | 7.66 | 7.69 | 7.66 | 7.80 | 8.30 | 8.99 | 8.75 | 8.67 | 8.56 | 8.38 |
| 6 | 8.36 | 8.79 | 9.18 | 9.52 | 9.73 | 9.82 | 9.83 | 10.00 | 10.62 | 11.53 | 11.22 | 11.10 | 10.91 | 10.62 |
| 7 | 9.65 | 10.24 | 10.80 | 11.29 | 11.64 | 11.82 | 11.93 | 12.16 | 12.94 | 14.09 | 13.75 | 13.60 | 13.37 | 12.99 |
| 8 | 10.76 | 11.55 | 12.19 | 12.86 | 13.34 | 13.66 | 13.84 | 14.11 | 15.01 | 16.35 | 16.01 | 15.86 | 15.63 | 15.22 |
| 9 | 11.77 | 12.63 | 13.59 | 14.42 | 15.03 | 15.47 | 15.73 | 16.05 | 17.09 | 18.61 | 18.25 | 18.08 | 17.81 | 17.33 |
| 10 | ≈ 12.68 | 13.78 | 14.91 | 15.91 | 16.69 | 17.25 | 17.60 | 18.00 | 19.17 | 20.88 | 20.50 | 20.31 | 20.01 | 19.46 |
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 20.504 |
| SC2 | 0 | 8 | 14.105 |
| SC3 | -18 | 7 | 11.449 |
| SC4 | -25 | 6 | 9.176 |
| SC5 | -34 | 6 | 8.458 |
| A | 2017 mm |
|---|---|
| B | 636 mm |
| C | 605 mm |
| F | 445 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 1685 mm |
| D IN | 1 x Ø22 |
| D OUT | 1 x Ø35 |
| Length | 2017 mm |
|---|---|
| Width | 636 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.